10. Digital and analogue input logic
• Digital inputs
1. Digital input 1 (
DI1
):
Parameter
M03
=0
Remote season changeover
contact
M04
=
0
1
Summer
Winter
M03
=1
Remote On/Off
M04
=
0
1
On
Off
M03
=2
Not occupied
M04
=
0
1
"Not occupied holiday" mode
Occupied mode
M03
=3
Economy mode
M04
=
0
1
No economy
Economy
M03
=4
Window contact
M04
=
0
1
Window open
Window closed
M03
=5
Alarm
M04
=
0
1
No alarm
Alarm active
M03
=6
Minimum thermostat
M04
=
0
1
Open
Closed
2. Digital input 2 (
DI2
):
Parameter
M05
=0
Remote season changeover
contact
M06
=
0
1
Summer
Winter
M05
=1
Remote On/Off
M06
=
0
1
On
Off
M05
=2
Not occupied
M06
=
0
1
"Not occupied holiday" mode
Occupied mode
M05
=3
Economy mode
M06
=
0
1
No economy
Economy
M05
=4
Window contact
M06
=
0
1
Window open
Window closed
M05
=5
Alarm
M06
=
0
1
No alarm
Alarm active
M05
=6
Minimum thermostat
M06
=
0
1
Open
Closed