19/126
Parameter
Description
Default
Min
Max
I54
Working season selection in 2-pipe system (
M01
=2, 5) with temperature of water sen-
sor between
I15
and
I16
(see paragraph
“12. Automatic season changeover with
water sensor (M01=2 or 5)” page 24
)
0= heating (on startup)
1= cooling (on startup)
2= season not defined, regulation stopped
0
0
2
I55
Low limit of scale for input 0...10V
0
-50
I56
I56
High limit of scale for input 0...10V
2000
I55
9999
I57
Unit of measure on display B for input 0...10V
0= ppm
1= %r.h.
2= without unit
0
0
2
I58
Correction for input 0...10V
AI3
0
-98.0
98.0
I59
Fan activation
It allows exclusion of the fan
0= fan not used
1= fan used
1
0
1
I60
BACnet mac address
3
0
254
I61
BACnet max masters
127
0
127
I62
BACnet low device ID
BACnet device ID = (
I63
x 10000) +
I62
7000
0
9999
I63
BACnet high device ID
BACnet device ID = (
I63
x 10000) +
I62
22
0
419