22/126
2. Analogue input 2
(AI2
)
Parameter
M09
=0
Remote internal
sensor
Sensor
AI2
is used in combination with the internal sensor to obtain the final regulation tem
-
perature in relation to the value of
I06
(see
“11. Regulation sensor(s)” page 24
).
M09
=1
Water sensor for
season changeover
I54
=0 or 1
I54
=2
Summer
Winter
Temp. water
I16
I15
Summer
Winter
Temp. water
I16
I15
0,5°C
[1,0°F]
0,5°C
[1,0°F]
On startup, if the water temperature sensor reading is between
I16
and
I15
, see paragraph
“12. Automatic season changeover with water sensor (M01=2 or 5)” page 24
M09
=2
Minimum thermostat
sensor
Minimum
thermostat
open
Minimum
thermostat
closed
I17
-
2°C
I17
Temp.
water coil
On startup, if the temperature of the heating coil is between
I17
and
I17
- 2, the minimum
thermostat is deemed to be open
M09
=3
Remote season
changeover contact
M10
=
0
1
Summer
Winter
M09
=4
Remote On/Off
M10
=
0
1
On
Off
M09
=5
Not occupied holi-
day
M10
=
0
1
“Not occupied holiday” mode
Occupied mode
M09
=6
Economy mode
M10
=
0
1
No economy mode
Economy mode
M09
=7
Window contact
M10
=
0
1
Window open
Window closed
M09
=8
Alarm
M10
=
0
1
No alarm
Alarm active
M09
=9
Sensor not used
For configurations
M09
from 3 to 8, analogue input 1 is used as a digital input. The contact is considered closed if it is shortcir-
cuited at the analogue input. The contact is considered open if there is no connection.
Note:
If one or more digital and/or analogue inputs are configured with the same control functionality, then the input with the higher
priority is considered.
Input priority:
Digital input 1 (
DI1
)
-
Highest priority
Digital input 2 (
DI2
)
Analogue input 1
(AI1
)
Analogue input 2
(AI2
)
Analogue input 3
(AI3
) -
Lowest priority