120/126
Multistate values
Object name
Object-ID
Description
Values / State text
Writable
AIR_DESTRAT_ACTIVATE
MULTISTATE_VALUE:2169
Air destratification function
1=OFF
2=ON on heat and cool
3=ON on heat
4=ON on cool
Yes
CONTROL_STATE
MULTISTATE_VALUE:2117
Unit regulation type
1=H
2=2-stage H
3=2-pipe, auto c/o
4=2-pipe, rem. contact c/o
5=2-pipe, par. c/o
6=2-pipe + R, auto c/o
7=2-pipe + R, rem. contact c/o
8=2-pipe + R, par. c/o
9=4-pipe
10=4-pipe + R
11=C
12=2-stage C
Yes
ELEC_HEATER_PRESENT
MULTISTATE_VALUE:2118
Electric resistance stage
1=No stage
2=Stage 1
3=Stage 2
4=Stage 1 and 2
Yes
DIG_INPUT1_FUNC
MULTISTATE_VALUE:2119
Digital input 1 function
Digital input 1 contact logic is
set on STATE_DI1 object with
property Polarity
1=Remote season c/o
2=Remote on/off
3=No occupied holidays
4=Economy
5=Window contact
6=Alarm
7=Minimum thermostat contact
8=Not used
Yes
DIG_INPUT2_FUNC
MULTISTATE_VALUE:2121
Digital input 2 function
Digital input 2 contact logic is
set on STATE_DI2 object with
property Polarity
1=Remote season c/o
2=Remote on/off
3=No occupied holidays
4=Economy
5=Window contact
6=Alarm
7=Minimum thermostat contact
8=Not used
Yes
ANALOG_INPUT1_FUNC
MULTISTATE_VALUE:2123
Analog input 1 function
Analog input 1 contact logic
is set on STATE_AI1_AS_DI3
object with property Polarity
(for values between 4 and 9)
1=Remote regulation sensor
2=Water sensor autom. season c/o
3=Minimum thermostat sensor
4=Remote season c/o
5=Remote on/off
6=No occupied holidays
7=Economy
8=Window contact
9=Alarm
10=Not used
Yes
ANALOG_INPUT2_FUNC
MULTISTATE_VALUE:2125
Analog input 2 function
Analog input 2 contact logic
is set on STATE_AI2_AS_DI4
object with property Polarity
(for values between 4 and 9)
1=Remote regulation sensor
2=Water sensor autom. season c/o
3=Minimum thermostat sensor
4=Remote season c/o
5=Remote on/off
6=No occupied holidays
7=Economy
8=Window contact
9=Alarm
10=Not used
Yes
ANALOG_INPUT3_FUNC
MULTISTATE_VALUE:2127
Analog input 3 function
Analog input 3 contact logic
is set on STATE_AI3_AS_DI5
object with property Polarity
(for values between 4 and 9)
1=Remote regulation sensor
2=Water sensor autom. season c/o
3=Minimum thermostat sensor
4=Remote season c/o
5=Remote on/off
6=No occupied holidays
7=Economy
8=Window contact
9=Alarm
10=Not used
11=0..10V
Yes
MIN_FAN_SPEED_OFF
MULTISTATE_VALUE:2159
Speed maintained when
setpoint reached
1=Fan stopped at set reached
2=Speed 1 on at set reached
3=Speed 1 on at set reached C.
4=Speed 1 on at set reached H.
5=Man. speed on at set reached
6=Man. speed on at set reached C.
7=Man. speed on at set reached H.
Yes