14. Working setpoint, ECONOMY mode and HOLIDAY mode
If a digital contact is configured as remote contact “not occupied holiday”
M03
=2 or
M05
=2 or a remote sensor is configured
as remote contact “not occupied holiday”
M07
=5 or
M09
=5 or
M11
=5, “not occupied holiday“ mode can be activated if the
corresponding contact is in the appropriate position (see digital and analogue input logic ).
Installations different from 4 pipe system (
M01
≠8 and 9):
In “not occupied holiday” mode, the heating setpoint is decreased by
I13
(see chart 2 pipe heating,
WHS
), the cooling setpoint
is increased by
I13
(see chart 2 pipe cooling,
WCS
).
Installations with 4 pipe system (
M01
=
8 and 9):
In “not occupied holiday” mode, the heating activation point is decreased by
I13
(see chart 4 pipe heating,
WHS
), the cooling
activation point is increased by
I13
(see chart 4 pipe cooling,
WCS
).
The icon is activated to indicate that “not occupied holiday” mode is active.
If one of the digital contacts is configured as remote contact “energy saving”
M03
=3 or
M05
=3 or a sensor is configured as
remote contact “energy saving”
M07
=6 or
M09
=6 or
M11
=6, energy saving mode can be activated if the corresponding contact
is in the appropriate position (see digital and analogue inputs logic).
Installations different from 4 pipe system (
M01
≠8 and 9):
In economy mode, the heating setpoint is decreased by
I12
(see chart 2 pipe heating,
WHS
), the cooling setpoint is increased
by
I12
(see chart 2 pipe cooling,
WCS
).
Installations with 4 pipe system (
M01
=
8 and 9):
In economy mode, the heating activation point is decreased by
I12
(see chart 4 pipe heating,
WHS
), the cooling activation
point is increased by
I12
(see chart 4 pipe cooling,
WCS
).
The “
ECO
“ icon is activated to indicate “energy saving” mode.
The “not occupied holiday” mode has priority over economy mode when both modes are activated.
Chart 2 pipe (analog output, cooling)
Chart 2 pipe (digital output, cooling)
100
0
Temp.
Outputs
BCS
(
I08
)
100
0
Temp.
Outputs
ON
OFF
Temp
Outputs
BCS
(
I08
)
ON
OFF
Temp
Outputs
(
I12
o
I13
)
(
I12
o
I13
)
WCS
WCS
WCS
WCS
ECONOMY
or
HOLIDAY
ECONOMY
or
HOLIDAY
100
0
Temp.
Outputs
BHS
(
I07
)
100
0
Temp.
Outputs
ON
OFF
Temp
Outputs
BHS
(
I07
)
ON
OFF
Temp
Outputs
(
I12
o
I13
)
WHS
WHS
WHS
WHS
ECONOMY
or
HOLIDAY
ECONOMY
or
HOLIDAY
(
I12
o
I13
)
100
0
Temp.
Outputs
BCS
(
I08
)
100
0
Temp.
Outputs
ON
OFF
Temp
Outputs
BCS
(
I08
)
ON
OFF
Temp
Outputs
(
I12
o
I13
)
(
I12
o
I13
)
WCS
WCS
WCS
WCS
ECONOMY
or
HOLIDAY
ECONOMY
or
HOLIDAY
100
0
Temp.
Outputs
BHS
(
I07
)
100
0
Temp.
Outputs
ON
OFF
Temp
Outputs
BHS
(
I07
)
ON
OFF
Temp
Outputs
(
I12
o
I13
)
WHS
WHS
WHS
WHS
ECONOMY
or
HOLIDAY
ECONOMY
or
HOLIDAY
(
I12
o
I13
)