37
UK
14 Maintenance / cleaning / change of medium
When removing or installing the unit for maintenance and cleaning work:
►
Make sure that the stainless steel tube clip is fixed to the sensor.
> It must be possible to exactly reproduce the installation height and position.
►
Remove the sensor and clean it / carry out maintenance
►
Install sensor exactly in the same position as before.
►
Otherwise check the parameter [OP] and carry out [cOP] once again.
14.1 Maintenance information for operation without overflow
prevention
[MEdI] = [Auto] or [OP] = [OFF] (overflow prevention OP deactivated)
The unit must be reinitialised in the following cases (switch the operating voltage
briefly off and on again):
• After all maintenance operations.
• After cleaning operations (e.g. water jet cleaning of the sensor probe).
• If the sensor was removed from the tank and then installed again during
operation.
• If the active zone of the sensor was touched with the hand or grounded objects
(e.g. a screwdriver, a cleaning lance).
• If the connection between the sensor and the tank wall/counter-electrode was
changed.
• After a change of the medium with considerably differing dielectric constants.
For manual selection of media, first the [MEdI] setting needs to be adjusted.