8
4.2 Example configuration 2
Unit
LT8023 (probe length L= 472 mm)
Medium to be detected
Coolant emulsion
Operating mode
Installation environment Metal tank, installation to Fig. 4-2.
►
Install unit.
►
Observe the distances (x), (u) and (c):
x:
min. 4.0 cm
u:
min. 1.0 cm
c:
max. 23.0 cm
►
Ground sensor and tank via an electrical
connection
►
Observe the maximum permitted level (b).
A distance (a2) greater than 5.0 cm must be
observed between maximum level (b) and
mounting element.
►
Observe the parameter setting sequence:
-[MEdI] = [Auto] (
)
-[OFS] = (u); e.g. (u) = 1.0 cm
-[SP1] = Set the switch point at a distance (a2)
Fig. 4-2
c
b
u
a2
x
Switch points [SP3] and [SP4] can be used to control the medium
temperature and to set limit values for early warning / alarm.
►
Unit must be reinitialised:
►
Switch the operating voltage off and on again.
> The unit is ready for operation.
►
Make further settings if necessary.
►
Check whether the unit operates correctly.