29
UK
With deactivated overflow prevention [MEdI] = [Auto] or [OP] = [OFF] it is
necessary for the unit for applying the basic settings and adaptation to the
medium and installation environment:
1. to be installed in the application.
2. to be reinitialised.
►
Switch the operating voltage off and on again.
10.3 Setting of output signals
10.3.1 Set output function [oux] für OUT1...OUT4
►
Select [oux] and adjust the switching function:
ou1
...
ou4
[Hno] = hysteresis function / normally open
[Hnc] = hysteresis function / normally closed
[Fno] = window function / normally open
[Fnc] = window function / normally closed
If the switching output is used as an overflow prevention, the setting [oux]
= [Hnc] (NC function) is recommended. The principle of normally closed
operation ensures that wire break or cable break is also detected.
10.3.2 Define the switching limits [SPx] / [rPx] (hysteresis function)
►
Make sure that the function [Hno] or [Hnc] is set for [oux].
►
Set [SPx] first, then [rPx].
►
Select [SPx] and set the value at which the output is set.
SP1
...
SP4
►
Select [rPx] and set the value at which the output resets.
rP1
...
rP4
[rPx] is always smaller than [SPx]. The unit only accepts values which are lower
than the value for [SPx]. If [SPx] is shifted, [rPx] also shifts provided that the lower
end of the setting range is not reached.