27
UK
►
In case of doubt, select [OIL.2] for oils.
►
Test proper functioning in an application test.
The settings [CLW.1] and [CLW.2] suppress deposits (e.g. metal swarf).
The settings [OIL.1] and [OIL.2] suppress a bottom layer of higher dielectric
water or swarf which is a few cm high. If no oil layer is present (or if it is
very thin), the bottom layer is detected.
With the setting [MEdI] = [Auto],
no
overflow prevention is available. In that case,
the menu items [OP] and [cOP] are not available.
10.2.7 Set the overflow prevention [OP]
►
Comply with minimum distances and installation instructions.
►
Select [OP].
►
Define the position of the overflow prevention OP.
The option [OP] = [OFF]
deactivates
the overflow prevention OP.
OP
►
Set [OP] before [SPx] or [FHx].
>
[SPx] / [FHx] decreases if [OP] is reduced to a value ≤ [SPx] / [FHx] after
setting [SPx] / [FHx].
> If [OP] and [SPx] / [FHx] are close to each other (1 x step increment),
[SPx] / [FHx] increases if [OP] increases.
When the overflow prevention is deactivated [OP] = [OFF] or [MEdI] =
[OFF] , the safe function of the sensor must be verified with particular care.
Switch-on and switch-off processes and special operating states such as
very full tanks, possible maintenance and cleaning operations are to be
considered in the verification.
For setting [OP] = [OFF] the menu item [cOP] is not available.