4.1 Example configuration 1
Unit
LT8022 (probe length L= 264 mm)
Medium to be detected
Mineral oil
Operating mode
Manual media selection with overflow prevention
Installation environment Metal tank, installation to Fig. 4-1
►
Install unit.
►
Observe the distances (x), (u) and (c):
Fig. 4-1
OP
c
x:
min. 4.0 cm
u:
min. 1.0 cm
c:
max. 14.0 cm
►
Ground sensor and tank via an electrical
connection
►
Observe the parameter setting sequence:
)
-[OFS] = (u); e.g. (u) = 2.0 cm
-[OP]: Set the overflow prevention OP at a
distance (y) greater than 4.5 cm below the
mounting element.
For distances (y) smaller than 4.5 cm there
may be malfunctioning and error messages
during the adjustment process [cOP].
Step increment and setting range:
.
Calculation aids for [OP]: (
).
►
Adjustment of the overflow prevention OP to [cOP]
.
> The unit is ready for operation.
►
Make further settings if necessary.
►
Check whether the unit operates correctly.