• If the level is below SP1, the output is switched. If the level is above SP1 or
if there is a wire break, output 1 switches off (alarm message "overflow / wire
break“).
• If the level exceeds SP2, output 2 switches (upper value exceeded;
submersible pump ON).
• If the level is below SP3, output 3 switches (lower value reached; submersible
pump OFF).
• Suggestion for temperature monitoring:
ou4 = Hnc
SP4 = 45 (°C)
rP4 = 40 (°C)
As long as the temperature is below SP4, the output switches. If the level is
above SP4 or if there is a wire break, output 4 switches off (alarm message
"overtemperature / wire break“).