26
10.2.3 Define unit of measurement for level [uni.L]
►
Enter [uni.L] before the limits for level are entered.
This avoids unintentional maladjustments.
►
Select [uni.L]
►
Define unit of measurement for the level:
uni.L
[cm] =
level in cm
[inch] =
level in inches
10.2.4 Set the unit of measurement for the temperature [uni.T]
►
Enter [uni.L] before the limits for temperature are entered.
This avoids unintentional maladjustments.
►
Select [uni.T]
►
Set unit of measurement for the temperature:
Uni.T
[°C] =
temperature in °Celsius
[°F] =
temperature in °Fahrenheit
10.2.5 Set the offset [OFS]
The distance between tank bottom and lower edge of the measuring probe can be
entered as offset value
►
Set [OFS] before entering the values for SPx, rPx or OP.
This avoids unintentional maladjustments.
►
Select [OFS].
►
Set the value for the offset.
Note the set unit of measurement [uni.L].
OFS
10.2.6 Set the medium [MEdI]
►
Select [MEdI] and set the corresponding sensitivity:
MEdI
[CLW.1] = water, hydrous media, coolant emulsions.
[CLW.2] = water, hydrous media, coolant emulsion for temperatures >
35 °C (installation in climatic tube).
[OIL.1] = oils with an increased dielectric constant (e.g. some synthetic
oils).
[OIL.2] = oils with a low dielectric constant (e.g. mineral oils).
[Auto] =
automatic medium detection.