Recommended adjustment:
•
Select TN according to the time response of the system (fast
system = small TN, slow system = big TN)
•
Increase KP slowly step by step up to a value at which no
oscillation will occur.
•
Readjust TN if necessary.
•
Add D part only if rquired: select TV approx. 2 - 10 times
smaller than TN. KD should be approx. the same as KP.
Please not that the max. deviation is +/- 127. To get a good
dynamic performance this range should not be exceeded, but
should be used as fully as possible.
Function input SO (self-optimisation) considerably improves the
control characteristics on the condition that the requested
features have been reached:
•
The controller is operated with I share (TN
≥
50 ms)
•
The parameters KP and especially TN are already well
adapted to the real controlled system.
•
The control range (X - XS) of +/- 127 is used (if necessary
extend the control range by multiplying X, XS and XMAX).
After the parameter settings have been finalised set SO =
TRUE. The control characteristics are considerably improved.
Overshooting in particular is reduced.