page 23
The programmer has to ensure that the same software level
of the operating system (CR..._x.H86), of the controller
configuration (CR..._x.M66) and the unit library (CR..._x.LIB)
are used. If not, an error message is generated during the
download of the application software. Software states are
marked by suffixed letters in alphabetical order in the file
name (e.g. CR0015_B.H86). The basic file always has to be
the same.
Operating system download
The operating system and the application software are loaded
directly from the programming system. The download can be
carried out via the serial and via the CAN interface. The
following points have to be observed:
New controller
On delivery, the controller module does not contain an operating
system. When the supply voltage is applied it therefore goes
into the state "No operating system loaded". Only the bootloader
is active
!"
For downloading activate the controller configuration screen
via the button or via the menu item
Window / PLC
Configuration.
!"
The requested controller configuration (CR..._x.M66) is
called via the menu item
Insert / Firmware.
!"
The connection between controller and PC can then be
established with
Online / Login
. The interface via which the
connection is made depends on the setting in
Extras / HW-
Config
(serial or CAN) and the following parameterisation of
the PC interface under
Online / Communication
Parameters..
.
A communication connection to the controller is only
established when a project is loaded and when this is
translated without errors.
!"
The download process is started by selecting the menu item
Extras / Load Hex file
and select file (CR..._x.H86) in the
screen
PLC Configuration
.
The new controller configuration file has to be used for all
application programs to be loaded in the controller.
Operating system update
In general, a new operating system software can be loaded in
the controller at a later time. This process corresponds in most
parts to the one described above.
As opposed to the delivery sate of the controller, an operating
system is loaded, i.e. the controller is in the STOP or RUN
mode.
!"
The controller configuration of the operating system loaded
at current time is activated so that the programming system
can establish the connection between controller and PC.
Содержание ecomat 100 R 360 Series
Страница 1: ...System manual ecomat 100 type R 360 ...
Страница 14: ...page 14 ...
Страница 26: ...page 26 ...
Страница 86: ...page 86 ...
Страница 100: ...page 100 ...
Страница 126: ...page 126 ...
Страница 146: ...page 146 ...
Страница 162: ...page 162 ...
Страница 163: ...page 163 Annex 2 Wiring Annex 2 1 Type CR0015 ...
Страница 164: ...page 164 Annex 2 2 Type CR0016 ...
Страница 165: ...page 165 Annex 2 3 Type CR0017 ...
Страница 166: ...page 166 Annex 2 4 Type CR0501 ...