page 22
4.2. Status LED
These operating states are shown with the integrated status
LED.
LED colour Flash frequency Description
LED off
constantly off
Fatal Error
green
5 Hz
no operating system loaded
green
0.5 Hz
Run, CANopen: PREOPERATIONAL
2.0 Hz
Run, CANopen: OPERATIONAL
constantly on
Stop, CANopen: PRERPARED
red
0.5 Hz
Run w. error (CANopen: PREOPERATIONAL)
2.0 Hz
Run w. error (CANopen: OPERATIONAL)
100 %
Reset checks or stop with error
The operating states STOP (PREPARED) and RUN (PRE-
OPERATIONAL
/
OPERATIONAL) can be changed by the
programming system or the network master.
The user program is processed in the RUN state. The controller
only takes part in the CANopen communication (PDO
processing, see chapter 6) when it is set to OPERATIONAL. To
see the current operating state in the application program the
user can evaluate the flag COP_PREOPERATIONAL. The flag
is TRUE when the state is PREOPERATIONAL, otherwise it is
FALSE.
4.3. Loading the operating sytem
When the unit is shipped an operating system is in general not
loaded in the controller (LED flashes green at 5 Hz). In this
operating state only the boot loader is active. It provides the
minimum functions for the loading process of the operating
system (e.g. the support of the serial and the CAN interface).
In General, the download of the operating system only has to be
carried out once. The application program can then be loaded in
the controller (even several times). The advantage of this
process is that the EPROM does not need to be replaced for an
operating system update and that customer-specific operating
system can be realised for certain applications.
The operating system is provided together with this
documentation on a separate data carrier.
Содержание ecomat 100 R 360 Series
Страница 1: ...System manual ecomat 100 type R 360 ...
Страница 14: ...page 14 ...
Страница 26: ...page 26 ...
Страница 86: ...page 86 ...
Страница 100: ...page 100 ...
Страница 126: ...page 126 ...
Страница 146: ...page 146 ...
Страница 162: ...page 162 ...
Страница 163: ...page 163 Annex 2 Wiring Annex 2 1 Type CR0015 ...
Страница 164: ...page 164 Annex 2 2 Type CR0016 ...
Страница 165: ...page 165 Annex 2 3 Type CR0017 ...
Страница 166: ...page 166 Annex 2 4 Type CR0501 ...