Function
NMS_GUARDING_CONFIG
Library
COB.LIB
Function symbol
Purpose
The guard time for a R 360 CANopen slave is set.
Parameters
Function inputs
Function outputs, none
Description
Via the function NMS_GUARDING_CONFIG the permitted
times for the node guarding and the SYNC objects can be set in
the R 360 CANopen slave during the initialization. To do so, the
function is called once. The execution of the function is
controlled by the function input ENABLE.
If within the specified times the corresponding objects (for node
guarding possibly x number of the lifetime cycles) are not
received by the R 360 slave, the corresponding error bits
(COP_GUARDFAIL_ERROR and COP_SYNCFAIL_ERROR)
are set. They must then be evaluated by the application
program.
Also, the flag COP_SYNC can be evaluated. It is always TRUE
for precisely one cycle.
The specified times must be a little greater than the times
set in the master.
Name
Data type Description
ENABLE
BOOL
TRUE: The function is processed.
FALSE: The function is not processed.
GUARDTIME
TIME
Time between two monitoring calls
0 ms = no monitoring
1ms .. 65535ms = monitoring time
LIFETIME
BYTE
Number of the permitted erroneous
monitoring calls
CYCLEPERIOD
TIME
Time between two SYNC objects
0 ms = no monitoring
1ms ... 65535ms = monitoring time
Содержание ecomat 100 R 360 Series
Страница 1: ...System manual ecomat 100 type R 360 ...
Страница 14: ...page 14 ...
Страница 26: ...page 26 ...
Страница 86: ...page 86 ...
Страница 100: ...page 100 ...
Страница 126: ...page 126 ...
Страница 146: ...page 146 ...
Страница 162: ...page 162 ...
Страница 163: ...page 163 Annex 2 Wiring Annex 2 1 Type CR0015 ...
Страница 164: ...page 164 Annex 2 2 Type CR0016 ...
Страница 165: ...page 165 Annex 2 3 Type CR0017 ...
Страница 166: ...page 166 Annex 2 4 Type CR0501 ...