page 21
4. States and operating system
4.1. Operating modes
When the supply voltage is applied, the controller module may
be in one of 5 possible operating modes:
Reset
This status is run through after each power-on reset. The
operating system is initialised. Different checks are carried out.
This status is only temporary and is superseded by the run
status.
!"
The LED is lit red for a short time (is lit orange starting with
software version CRxxxx_G).
Run
This status is reached:
•
from the reset status (Autostart)
•
from the stop status by means of the run command
prerequisite: test mode
•
with the CANopen NMT master via the function
PREOPERATIONAL or OPERATIONAL
!"
The LED flashes green or red (RUN with error)
Stop
This status is reached:
•
from the reset status if no program is loaded
•
from the run status by giving the stop command via the
interface
Prerequisite: test mode
•
with the CANopen NMT master via the function
PREPARED.
!"
The LED is constantly lit green or red (stop with error)
Fatal Error
The controller passes into this status if a non-tolerable error is
found. This status can only be left via a reset.
!"
The LED is off (is lit red starting with software version
CRxxxx_G).
No operating system
No operating system has been loaded, the controller is in the
bootloading status. Before loading the application software a
download of the operating system must be carried out.
!"
The LED flashes green (fast).
Содержание ecomat 100 R 360 Series
Страница 1: ...System manual ecomat 100 type R 360 ...
Страница 14: ...page 14 ...
Страница 26: ...page 26 ...
Страница 86: ...page 86 ...
Страница 100: ...page 100 ...
Страница 126: ...page 126 ...
Страница 146: ...page 146 ...
Страница 162: ...page 162 ...
Страница 163: ...page 163 Annex 2 Wiring Annex 2 1 Type CR0015 ...
Страница 164: ...page 164 Annex 2 2 Type CR0016 ...
Страница 165: ...page 165 Annex 2 3 Type CR0017 ...
Страница 166: ...page 166 Annex 2 4 Type CR0501 ...