IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
89
Supported services
34377
Service code
Name
Class
Attribute
Description
dec
hex
01
01
Get_Attribute_All
yes
yes
Read all attributes
05
05
Reset
yes
yes
Reset
14
0E
Get_Attribute_Single
yes
yes
Read single attribute
16
10
Set_Attribute_Single
yes
yes
Change single attribute
If an Identity Object receives a reset request, it carries out the following actions:
It checks if it supports the requested reset type.
It responds to the request.
It tries to execute the requested reset type.
Supported reset types:
0
Reboot the device (obligatory for all EtherNet/IP devices).
1
Restore factory settings and reboot the device.