IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
82
>
Command 0x20
– Set validation ID / data storage
34321
The command sets the behaviour of the IO-Link master when connecting a new IO-Link device to an
IO-Linkport of the device.
Corresponding parameter: [Validation ID] (
→
Mapping: Port configuration
(
>
Command request
34315
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
4
Port No. (LSB)
5
Port No. (MSB)
6
reserved
7
reserved
8
reserved
9
reserved
10
Trigger
0x20
11
Validation ID
12...42
reserved
Legend:
[Port No.]
Number of the IO-Link port
Port No. = 0x1234
Port No. (MSB) = 0x12
Port No. (LSB) = 0x34
2 byte
0x01
Port X01
0x02
Port X02
...
0x04
Port X04
[Trigger]
Control command execution
1 Bit
0x0
do not process command
0x1
execute command
[Validation ID]
Behaviour of the IO-Link master when
connecting an IO-Link device to the IO-Link port
1 byte
0x0
No check
0x1
Type compatible V1.0 Device
0x2
Type compatible V1.1 Device
0x3
Type compatible V1.1 Device with
Restore
0x4
Type compatible V1.1 Device with
Restore