IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
81
>
Command response
34316
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
4
Port No. (LSB)
5
Port No. (MSB)
6
reserved
7
reserved
8
reserved
9
reserved
10
Handshake
0x10
11
Result
12
Target Mode
13...45
reserved
Legend:
[Port No.]
Number of the IO-Link port
Port No. = 0x1234
Port No. (MSB) = 0x12
Port No. (LSB) = 0x34
2 Byte
0x01
Port X01
0x02
Port X02
...
0x04
Port X04
[Handshake]
Status of the execution of the command
1 Bit
0x0
command is executed
0x1
execution of the command was
successful
[Result]
Error indication
1 Byte
0x00
no error
0x01
error occured
[Target Mode]
Operating type of the IO-Link port
1 Byte
0x00
deactivated
0x01
operation as digital input (DI)
0x02
operation as digital output (DO)
0x03
operation as IO-Link intervals