IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
80
>
Command 0x10
– Set mode
34322
The command changes the operating mode of an IO-Link port of the AL1120.
Corresponding parameter: [Port Mode] (
→
Mapping: Port configuration
(
>
Command request
34314
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
4
Port No. (LSB)
5
Port No. (MSB)
6
reserved
7
reserved
8
reserved
9
reserved
10
Trigger
0x10
11
Target Mode
12...45
reserved
Legend:
[Port No.]
Number of the IO-Link port
Port No. = 0x1234
Port No. (MSB) = 0x12
Port No. (LSB) = 0x34
16 Bit
0x01
Port X01
0x02
Port X02
...
0x04
Port X04
[Trigger]
Control of the command execution
1 Bit
0x0
do not process command
0x1
execute command
[Target Mode]
Operating type of the IO-Link port
8 Bit
0x00
deactivated
0x01
operation as digital input (DI)
0x02
operation as digital output (DO)
0x03
operation as IO-Link intervals