IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
29
>
9.1.5
Fieldbus: set the configuration mode
54693
The AL1120 supports the EtherNet/IP configuration modes "top-down" and "independent".
Additionally, the user can configure the length of the transmitted process data and select the required
connection types.
►
Select [Fieldbus] menu.
>
The menu page shows the current settings.
►
Set the following parameters as required:
Name
Description
Possible values
[Configuration]*
EtherNet/IP configuration mode
Independent mode off
Configuration via fieldbus PLC
Independent mode on
Configuration via AL1120
[Process data length]*
Length of process data per IO-Link
port
2 bytes input 2 bytes
output
2 bytes input data, 2 bytes output
data
4 bytes input 4 bytes
output
4 bytes input data, 4 bytes output
data
8 bytes input 8 bytes
output
8 bytes input data, 8 bytes output
data
16 bytes input 16 bytes
output
16 bytes input data, 16 bytes output
data
32 bytes input 32 bytes
output
32 bytes input data, 32 bytes output
data
[Swap]*
Sequence of bytes in the data
word
off
as Array of Bytes
on
as Integer16 value; during an
update of the process data, the
bytes are exchanged
[Explicitpdmode]**
Enable / disable explicit PD mode
and select the process data to be
transmitted (connection types)
Explicit process data
mode off
Explicit PD mode disabled
Explicit process data
mode with IO-Link I/O +
A Diag
Explicit PD mode enabled: IO-Link
inputs /outputs, acyclic data and
diagnostic data are transmitted
Explicit process data
mode with IO-Link I/O +
Acyclic
Explicit PD mode enabled: IO-Link
inputs/outputs and acyclic data are
transmitted
Explicit process data
mode with IO-Link I/O
Explicit PD mode enabled: IO-Link
inputs/outputs are transmitted
* ... Parameter can only be changed if the EtherNet/IP controller is disconnected
** ... Parameter only valid if [Configuration] = [Independent mode on]
►
Save changed values on the device.