IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
60
>
Configuration Assembly (Instance 199)
34363
The values of the Configuration Assembly are set in RSLogix 5000 via the controller tags of
the EtherNet/IP project.
Byte
Content
0
Access rights
1
Process data length
2...13
X01: Port configuration (
→
Mapping: Port configuration
(
→ S.
14...25
X02: Port configuration (
→
Mapping: Port configuration
(
→ S.
26...37
X03: Port configuration (
→
Mapping: Port configuration
(
→ S.
38...49
X04: Port configuration (
→
Mapping: Port configuration
(
→ S.
Legend:
[Access Rights]
Access rights to parameter, process data
and events / diagnostics data of the
IO-Link master and the connected
IO-Link devices
1 Byte
0x00
EtherNet/IP + IoT
0x01
EtherNet/IP + IoT (ro)
0x02
EtherNet/IP only
0x03
Keep setting (default)
[Process Data
Length]
Length of the process input data and
process output data
1 Byte
0x00
2 Bytes Input / 2 Bytes Output Data
Input Assembly: 126 Bytes
Output Assembly: 54 Bytes
0x01
4 Bytes Input / 4 Bytes Output Data
Input Assembly: 134 Bytes
Output Assembly: 62 Bytes
0x02
8 Bytes Input / 8 Bytes Output Data
Input Assembly: 150 Bytes
Output Assembly: 78 Bytes
0x03
16 Bytes Input / 16 Bytes Output Data
Input Assembly: 182 Bytes
Output Assembly: 110 Bytes
0x04
32 Bytes Input / 32 Bytes Output Data
Input Assembly: 246 Bytes
Output Assembly: 174 Bytes