8.8.2
Set variable components of the response time
43045
The variable components influencing the process safety time of the entire system can be set by the
user at the following nodes in the CODESYS project:
T(MainTask):
Location: standard area of device tree
Node: [MainTask]
Parameters: [Interval]
*T(SafetyTask):
Location: safety extension of the device tree
Node: [Safety Task]
Parameters: [Cycle time]
T(MapTask):
Location: standard area of device tree
Node: [MapTask]
Parameters: [Interval]
T(WD_SafetyNetVars):
Location: safety extension of the AS-i device tree
Node: safety network variable (receiver)
Parameters: [Watchdog Time]
T(WD_FSoE):
Location: safety extension of the AS-i device tree
Node: [Logical I/Os] > safe EtherCAT module
Parameters: [Watchdog Time]
>