9.1.1
Download Standard application to AC4S
43292
If standard network variables and safety network variables are used simultaneously:
→
Note: Projects with network variables
(
To transfer standard application of the CODESYS project to AC4S:
Requirements:
>
Communication path of Standard PLC is correctly set (→
Configure programming interface
>
All ifm system solutions on the device were deleted (→ Device manual:
ifm-Apps deinstallieren
).
1 Download standard application to the device
►
In standard area of device tree:
Mark standard application and activate with [Project] > [Set active application].
►
Select [Online] > [Login].
>
CODESYS changes to the online mode.
>
CODESYS compiles standard application and transfers it to AC4S.
2 Start standard application
►
Start [Application].
>
[Application] is in the RUN mode.
3 Optional: Create boot application
►
Select [Online] > [Create boot application].
>
CODESYS stores standard application non-volatilely on AC4S.
If the parameter "Create implicit boot application on download" is activated in the features of
the application, step 3 is not necessary any more.
To check if the parameter is active:
►
Mark [Application].
►
Select [View] > [Properties...].
>
Tab [Boot application] shows the current parameter value.