SmartPLC SafeLine AC4S with fieldbus interfaces
234
>
SF_OUTcontrol_ASi
43114
Device type:
AS-i slave (output)
Library:
sf_logicalinterfaces.library
Symbol in CODESYS:
>
Description
43298
Logical device for a safe AS-i control slave (ASi_SlaveAdr, ASi_Master)
SF_OUTControl_ASi generates a safe output signal (S_OUT) from the configured process data value.
The safe output signal controls the AS-i control slave that generates a safe code sequence with which
one or several safe AS-i output slaves can be enabled.
The programmer can activate the following functions:
DisableLogging:
Only error events are transmitted to the online support centre (OSC) of the AC4S user interface.
>
Parameter data
43053
Parameter
Data type
Description
Possible values
ASi_SlaveAdr
INT
Address of the AS-i slave
1
...
31
Slave address 1
...
slave address 31
ASi_Master
INT
AS-i master to which the AS-i
slave is connected
1
AS-i Master 1
2
AS-i Master 2
DisableLogging
BOOL
Transmission of the event
messages to OSC of the device
FALSE
Following states of the state diagram
are transmitted to the OSC: *
S_ON
S_OFF
S_Test
S_Error
S_Init (HW-Error)
TRUE
Following states of the state diagram
are transmitted to the OSC:
S_Test
S_Error
S_Init (HW-Error)
* ...
Default value
>
Process data
43117
Parameter
Data type
Description
Possible values
S_OUT
SAFEBOOL
Release of the safe AS-i output
slave
FALSE
safety function OFF
TRUE
safety function ON