SmartPLC SafeLine AC4S with fieldbus interfaces
113
>
Reset the standard application (warm)
42524
To reset the standard application on the Standard PLC, choose one of the following options:
CODESYS: command [Reset (warm)]
►
In the standard area of device tree:
Highlight the required standard application as active application.
►
Select [Online] > [Login] to establish a connection to the CODESYS Standard PLC.
>
CODESYS switches to online mode.
►
Select [Online] > [Reset warm] to reset the standard application.
GUI: command [Reset]
►
>
►
Select [All Applications] tab.
►
Use [Reset] to reset all standard applications.
>
Reset the Standard application (cold)
42526
To reset the standard application on the Standard PLC, choose one of the following options:
Download the standard application to the device
►
→
Download standard applciation to AC4S
CODESYS: command "Reset (cold)"
►
In the standard area of device tree:
Highlight the required standard application as active application.
►
Select [Online] > [Login] to establish a connection to the CODESYS Standard PLC.
>
CODESYS switches to online mode.
►
Select [Online] > [Reset cold] to reset the standard application.
>
Reset the Standard application (origin)
42527
To reset the standard application on the Standard PLC:
CODESYS: command "Reset (origin)"
►
In the standard area of device tree:
Highlight the required standard application as active application.
►
Select [Online] > [Login] to establish a connection to the CODESYS-Standard PLC.
>
CODESYS switches to online mode.
►
Select [Online] > [Reset origin] to reset the standard application.