SmartPLC SafeLine AC4S with fieldbus interfaces
160
>
Output parameters
42542
Parameter
Data type
Description
Possible values
xReady
BOOL
Signal indicates whether the execution
of the FB is completed.
FALSE
FB is inactive or being
executed.
TRUE
FB execution is completed.
xBusy
BOOL
Signal indicates whether the FB is
being executed.
FALSE
FB is deactivated or FB
execution is completed.
TRUE
FB execution has started but is
not yet completed.
xError
BOOL
Signal indicates whether errors
occurred while the FB was executed.
FALSE
FB is disabled or is being
executed or FB was executed
without error.
TRUE
An error occurred while the FB
was executed.
wDiagnostic
WORD
Diagnostic information
→ List below (Diagnostic codes)
Diagnostic codes:
0x0000
No specific error is set
0x0001
Slave does not respond or change to offline mode during FB execution
0x000A
Sslave not in LAS
0x000B
Data content invalid (e.g. parameter value >7 for A/B slaves)
0x000E
Invalid slave address (e.g. 0 or 0B specified)
0x0018
Master is not in normal operation.