WindO/I-NV4 User’s Manual
3-39
5 User Communication
3
Communic
ation
■
Trigger Condition
Set the trigger conditions for transmission or receiving of data.
TXD
is selected as
Type
:
RXD
is selected as
Type
:
Trigger Type:
A condition for data transmission is selected from the following.
Rising-edge: Data is transmitted when the value of device address changes from 0 to 1.
Falling-edge: Data is transmitted when the value of device address changes from 1 to 0.
Satisfy the condition:
Data is transmitted when the condition changes from not satisfied to satisfied.
Fixed Period: Data is transmitted at a fixed time interval.
Data Type:
Select the data type handled by the conditional expression.
Can only be set if
Satisfy the condition
is selected as
Trigger Type
.
For details, refer to Chapter 2 “1.1 Available Data” on page 2-1.
Device Address: Specifies the bit device or the bit number of the word device to serve as condition. You can only
specify the internal device.
Can only be set if
Rising-edge
or
Falling-edge
is selected as
Trigger Type
.
Click
to display the Tag Editor. For the device address configuration procedure, refer to Chapter
2 “5.1 Device Address Settings” on page 2-68.
Condition:
Sets the condition formula.
Can only be set if
Satisfy the condition
is selected as
Trigger Type
.
Click
to display the Trigger Condition Settings dialog box. For the conditional expressions
configuration procedure, refer to Chapter 2 “5.2 Setting Conditional Expressions” on page 2-71.
Period (sec):
Specify the period for command execution from 1 to 3600 (seconds).
This is enabled only when
Fixed Period
is selected in
Trigger Type
.
Trigger Type:
Selects the condition to be ready to receive data from the following.
Always Enabled: The MICRO/I is always ready to receive data.
While ON:
Ready to receive data when the value of device address is 1.
Value of Device Address
1
0
Action
Execution
Execution
Execution
1
0
Value of Device Address
Action
Execution
Execution
Action
Execution
Condition
Satisfied
Not satisfied
Execution
Execution
Fixed time interval
Fixed time interval
Fixed time interval
Action
Execution
Execution
Execution
Action
Always Enabled
Value of Device Address
1
0
Enabled
Enabled
Enabled
Action
Содержание MICRO/I HG4G-CJT22 F-B Series
Страница 1: ...B 1701 11 User s Manual ...
Страница 26: ...Preface 25 WindO I NV4 User s Manual ...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic Font ANSI 1257 Cyrillic Font ANSI 1251 ...
Страница 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Страница 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Страница 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Страница 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Страница 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Страница 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Страница 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Страница 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Страница 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Страница 1286: ...4 Clear 24 26 WindO I NV4 User s Manual 4 Click Yes 5 Click Close This concludes clearing data ...
Страница 1288: ...4 Clear 24 28 WindO I NV4 User s Manual 6 Click Yes 7 Click Close This concludes clearing data on the external memory device ...
Страница 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Страница 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Страница 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Страница 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Страница 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Страница 1664: ...Index 12 WindO I NV4 User s Manual ...