WindO/I-NV4 User’s Manual
15-17
3 Operation Log Settings Dialog Box
15
Oper
ation Log Function
■
Real Time
Select this check box to output data to the external memory device
in real time.
With real time output, data is saved to the external memory device
in three minute intervals after the MICRO/I starts
running. If the accumulated data reaches 80% of the amount set in the Data Storage Area, then the data is forcibly
saved to the external memory device
. When there is already data with the same file name on the external memory
device
, data is appended to that file. If there was no update to the data during the three minutes, it is not output.
Data is appended to the file until the size of the file reaches the restriction size (256 MB), so the maximum amount of
output data varies based on the settings for the output channel such as the amount of data, the data size, and the labels.
If the interval events occur more quickly than the time it takes to accomplish the real time output (the interval for writing
to the external memory device
), the Operation Log is recorded up to the data storage amount - 1, and then
afterwards, old data is discarded in order and replaced with new data.
*1 SD memory card for HG5G/4G/3G/2G-V, HG4G/3G and HG2G-5F, USB flash drive for HG2G-5T and HG1G/1P
MICRO/I
Operation Log data
(CSV)
Output to
External memory device
Operation Log data
Sampling Time
User
Screen No.
Event Name
Part Name
Details
Changed to
12/01/2011 12:00:10
-
Base1
Power ON
-
-
-
12/01/2011 12:01:23
User1
Base1
Switch to Base Screen
-
-
Base2
12/01/2011 12:02:45
User1
Base2
Change Users
-
-
User2
12/01/2011 12:03:06
User2
Base2
Change Operation Modes
-
-
System Mode
12/01/2011 12:04:11
User2
Base2
Press buttons
BitSwitch
-
-
12/01/2011 12:04:11
User2
Base2
Write Data to any Device Addresses
-
LDR0
55
12/01/2011 12:07:30
User2
Base2
Switch to Base Screen
-
-
Base3
3 minute interval
after operation starts
Data to be output
3 minutes after
operation starts
Data to be output
3 minutes
after that
Data to be output
after another
3 minutes
External memory device
USB flash drive
SD memory card
Real time output stops when the file size of the Operation Log data exceeds 256 MB or when there is
insufficient space on the external memory device. The error information is stored in the following HMI
Special Data Registers. For details about the error information, refer to Chapter 33 “HMI Special Data
Register (LSD)” on page 33-7.
SD memory card:
USB flash drive:
LSD42
LSD33
• When the value of the following HMI Special Internal Relays changes from 0 to 1, the data at that time is
first output in real time to the external memory device, and then access to the external memory device is
stopped. For details, refer to Chapter 33 “HMI Special Relay (LSM)” on page 33-2.
SD memory card:
USB flash drive:
LSD20
LSD18
• The amount of free space on the external memory device is saved to the following HMI Special Data
Registers. For details about the free space on the External Memory Devices, refer to Chapter 33 “HMI
Special Data Register (LSD)” on page 33-7.
SD memory card:
USB flash drive:
LSD43, 44
LSD34, 35
Содержание MICRO/I HG4G-CJT22 F-B Series
Страница 1: ...B 1701 11 User s Manual ...
Страница 26: ...Preface 25 WindO I NV4 User s Manual ...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic Font ANSI 1257 Cyrillic Font ANSI 1251 ...
Страница 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Страница 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Страница 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Страница 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Страница 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Страница 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Страница 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Страница 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Страница 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Страница 1286: ...4 Clear 24 26 WindO I NV4 User s Manual 4 Click Yes 5 Click Close This concludes clearing data ...
Страница 1288: ...4 Clear 24 28 WindO I NV4 User s Manual 6 Click Yes 7 Click Close This concludes clearing data on the external memory device ...
Страница 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Страница 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Страница 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Страница 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Страница 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Страница 1664: ...Index 12 WindO I NV4 User s Manual ...