Concord CXA/H -
Installation and Servicing
29
FAULT FINDING
FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING
NO
Secure and tighten
NO
48 PILOT LIT BUT NO MAINS GAS
Are the plugs on the gas valve(s) secure
and tight ?
YES
Are the connections at the plug-in terminal strip
at the control box secure ?
Fit new gas valve
NO
YES
Is there 230V ±10% at the gas valve plug(s) ?
YES
Fit new S4561B1054 PCB
NO
Refer to installation instructions for details.
49 BOILER GOES OUT ON OVERHEAT THERMOSTAT
Are the thermostat sensors in their correct
pockets ?
YES
Is there an unswitched live supply to terminal L1
on the plug-in terminal connection at the
control box ?
Is the pump (or shunt pump) wired to terminal
L
2
in the control box ?
NO
YES
Is there sufficient open circuit water volume
or load available on boiler shut down for the
pump overrun ?
YES
Refer to installation instructions
Has boiler thermostat knob been switched to
off ? (this overrides the pump overrun facility)
YES
Replace PCB W4115A1020.
NO
YES
Advise USER
Has the red overheat thermostat reset button
(located on thermostat housing) been reset?
YES
NO
Press red overheat thermostat button to reset
157290-3.pmd
11/7/2005, 11:10 AM
29