background image

Concord CXA/H - 

Installation and Servicing

19

SERVICING

(CXA 120/H boiler only)

Remove four M5 securing screws retaining internal turning
baffles from side of collector hood.  Slide turning baffles to rear

of collector hood void to facilitate access to flue ways for

cleaning.

27 SERVICING

Caradon Ideal Limited

 does not accept any liability

resulting from the use of unauthorised parts or the repair
and servicing of appliances not carried out in accordance
with the Company’s recommendations and specifications.

A comprehensive service should be carried out at least
once a year.  The User is advised to make a contract with
the local Gas Region or a CORGI registered heating
installer.

WARNING.

  ALWAYS turn 

OFF

 the gas supply at the gas

cock and switch 

OFF 

and disconnect the electricity supply

to the appliance BEFORE SERVICING OR REPLACING
ANY COMPONENTS.

Unscrew the extended nuts at the top of the NOx
duct behind the control box and lift the NOx duct
clear of the burners as illustrated below.

Undo the 4 wing nuts securing the burner front
plate.  Pull the front plate forwards, at the top,
and lift it out - taking care not to damage the
insulation.

The centre and RH burners can be lifted out
after they have been pushed back to clear the
injector.

To remove LH burner the pilot gas pipe
connection at the gas valve must be removed.
The LH burner may now be removed by
pushing it back to clear the injector and lifting it
out. To remove it away from the boiler, the flame
detector lead and spark lead must be
disconnected in the control box.

Remove the 2 screws securing the control box
door, lift it and carefully drop it down. Pull off the
flame detector lead and the spark electrode
lead connections from the S4561B1054 PCB
(the left hand board). Undo the strain relief
clamp and feed the sleeved leads out of the
box. The burner can now be fully removed from
the boiler.

Undo the screws securing the clean out cover
and lift it off to give access to the flue ways.

CLEANING THE BOILER.   Refer to Frame 5

Pull and lift off the lower front panel and top panel from
the boiler casing.

Con

1943

NOx duct

Con 1944

Baffle

Baffle

4, Baffle screws

4, Cover screws

Remove all loose deposits from the heat exchanger,
especially from between the fins, using the brush provided,

and remove all debris from the combustion chamber floor.

Examine the burner assembly.  Clean the burner bars by
brushing them down with a stiff bristle (not wire) brush.  Check

each bar carefully to ensure that all flame ports are clear, that

there are no cracks and that all surfaces are free from
accumulated deposits.

If available, an industrial vacuum cleaner may be useful to

assist in this work.  When cleaning the burner bars, take care

to avoid damage from rough handling to the pilot pipe,
electrodes and leads.

Inspect the pilot burner, injector, ignition electrode, and flame

detector electrode.

Ensure that they are clean and in good condition.
In particular, check that:

1.

The pilot burner is firmly secured.

2.

The pilot shield is clean and correctly positioned.

(Not fitted to the CXA 120/H boiler).

3.

The ignition electrode and lead are clean, undamaged,
secure and correctly dimensioned.  Refer to diagram in

Frame 28.

4.

The flame detector electrode and lead is clean,

undamaged, secure and correctly dimensioned. Refer
to Frame 28.

5.

The pilot burner head is clean and undamaged.

Note. Casing omitted for clarity

SER

VICING

Содержание Concord CXA 40/H

Страница 1: ......

Страница 2: ...1078 Water content litre 22 30 30 37 37 45 45 53 53 gal 4 8 6 6 6 6 8 2 8 2 9 9 9 9 11 7 11 7 Table 2 General Data This value is in the UK government s Standard Assessment Procedure SAP for energy ra...

Страница 3: ...he law is complied with The Concord CXA 40 H 120 H range of boilers has been tested and certified by British Gas to prEN656 for use with Natural gas only Multiple boiler installations The Concord CXA...

Страница 4: ...is designed to protect the boiler and may not necessarily protect the remote parts of the system OPTION KITS Remote indication kit This kit gives the facility of remote indication of the boiler statu...

Страница 5: ...rrun litres Relationship between load and water volume for the minimum capacity of water circuit during the 6 minute pump overrun period for different boiler outputs Graph 1 Heat Load Water Volume CXA...

Страница 6: ...into the expansion cistern must be avoided The above circuit capacity during pump overrun may be achieved either by provision of an adequate bypass circuit or by ensuring that a zone of suitable size...

Страница 7: ...2 BS 6281 Part 1 BS 6282 Part 1 BS 6283 Part 4 Working pressure 6 bar maximum Particular reference should be made to BS 6644 Section 6 and Guidance note PM5 Automatically controlled steam and hot wate...

Страница 8: ...less steel rigid or flexible flue liner grade 304 316 may be used in conjunction with a 50 mm minimum thick layer of vemiculite or perlite granules between the liner and the inner skin of the chimney...

Страница 9: ...ssembled boiler body with distributor tube on a wooden pallet base enclosed in a wooden crate 2 Carton containing the casing fastenings and flue brush 3 Carton containing the installation pack and ins...

Страница 10: ...and the flow tapping d Complete the water connections by plugging the 2 front top tappings with the 2 BSP plugs provided 1 Fit the distributor tube supplied with the boiler into one of the return conn...

Страница 11: ...stat phial and control sensor are correctly secured in the pockets Refer to Frame 13 9 SYSTEM CONNECTIONS One flow and return connection should be made to the rear of the boiler either on one side or...

Страница 12: ...stat pocket adjacent to the flow connection Fit the plastic Heyco bush over the sensor lead at the line shown and insert it into the thermostat pocket Ensure that the Heyco bush is correctly located 1...

Страница 13: ...unswitched live supply which the boiler requires to allow the pump overrun facility to operate should be controlled by the above switched fused supply but should connect from there directly to the boi...

Страница 14: ...14 Concord CXA H Installation and Servicing INSTALLATION 16 INTERNAL WIRING br brown r red LEGEND b blue bk black y yellow w white y g yellow green or orange v violet pk pink INSTALLATION...

Страница 15: ...any zone may be the load during overrun all zones MUST individually be able to satisfy the conditions in the foregoing paragraph If not all zones can do this then consider other means of control deta...

Страница 16: ...now calls for heat its thermostat will open Zone 1 valve via the normally open contacts of the relay IMPORTANT Terminal L2 may control the appropriate pump s directly provided that the total running...

Страница 17: ...2 minutes Any leaks must be cured Replace all pressure test point screws 21 INITIAL LIGHTING 1 Check that the boiler thermostat knob on the control box is OFF 2 Ensure that the main gas inlet cock is...

Страница 18: ...ectly to manual on off operations of any controls fitted in the gas control circuit Check in the following manner the operation of the flame failure safety device 1 Extinguish the main burner and pilo...

Страница 19: ...door lift it and carefully drop it down Pull off the flame detector lead and the spark electrode lead connections from the S4561B1054 PCB the left hand board Undo the strain relief clamp and feed the...

Страница 20: ...on the inside of the casing front panel and check the gas connections for tightness as detailed under Testing for Gas Soundness Frame 20 Check gas pressures and the gas rate test as instructed in Fra...

Страница 21: ...Frame 27 2 Both RH and centre burners can be removed by sliding each one back to clear the injector and then lifting out 3 To exchange the LH burner remove it from the boiler as previously described...

Страница 22: ...35 BURNER AND CONTROLS ASSEMBLY Exploded View CXA 40 H 80 H 36 BURNER AND CONTROLS ASSEMBLY Exploded View CXA 90 H 120 H LEGEND 1 Main gas inlet cock 2 Gas inlet union 3 Gas control valves 4 O ring s...

Страница 23: ...uit board and release cable clamp from the back panel 5 Pull the sensor lead through the grommeted hole in the back panel and the wire clips 6 Fit the new sensor and reassemble in reverse order ensuri...

Страница 24: ...he lower front panel 2 Undo the 2 screws securing the control box front panel Carefully lift it up and lower down 3 Pull off the 2 plugs and 3 push on connections from the board The board can now be r...

Страница 25: ...e part Gloves supplied with the spare part 1 Damp down the combustion chamber area containing the insulation boards 2 Remove the insulation boards The replacement boards are supplied in a plastic bag...

Страница 26: ...remove the left hand burner the pilot gas pipe connection at the gas valve must be removed 4 The left hand burner may now be removed by pushing it back to clear the injector and lifting it out taking...

Страница 27: ...bly are not fixed together therefore CARE MUST BE TAKEN TO PREVENT the installed section coming apart 8 Repeat the above procedure for all of the remaining sections until the assembly is complete 9 Fi...

Страница 28: ...sk which has required the breaking and remaking of electrical connections the following checks MUST be repeated Check that the gap between the electrode and pilot burner is 3 4 mm Ensure that the H T...

Страница 29: ...OES OUT ON OVERHEAT THERMOSTAT Are the thermostat sensors in their correct pockets YES Is there an unswitched live supply to terminal L1 on the plug in terminal connection at the control box Is the pu...

Страница 30: ...ctor 1 077 105 28 Pilot burner injector HONEYWELL 45900421 011 1 004 545 29 Gas control valve HONEYWELL V4601 AB 1034 1 154 810 Gas control valve HONEYWELL VR4605 AB 1019 CXA 90 120 H 1 111 869 Gas va...

Страница 31: ...2 CXA 80 H 1 111 652 CXA 90 100 H 1 111 653 CXA 110 120 H 1 154 898 50 Casing top panel white stove enamel CXA 40 H 1 111 293 CXA 50 H 1 111 294 CXA 60 H 1 111 295 CXA 70 H 1 111 296 CXA 80 H 1 111 29...

Страница 32: ...inuing improvement in the design and performance of its products The right is therefore reserved to vary specification without notice The Ideal Boilers Technical Training Centre offers a series of fir...

Отзывы: