Ecomod Heat Pump Control -
Installation and Servicing
Line No.
Value
• Timer programme 4/DHW
menu
Preselection
Preselection (560) Monday-Sunday
Adjust the timer programming
1st phase ON (561) 00: 00 h
Adjust the timer programming
1st phase Off (562) 06: 00 h
Adjust the timer programming
2nd phase ON (563) 22: 00 h
Adjust the timer programming
2nd phase Off (564) 24: 00 h
• LPB network
menu
Number of the appliance (preset)
Appliance address
(6600) 1
Number of the segment (preset)
Segment address
(6601) 0
Adjust the clock rate
Clock operation (6640) Master
•
Switch the DHW rate to automatic
Heat Pump No. 2:
Line No.
Value
• Configuration
menu
Preset the model of heating heat pump
Preset (5700) AHP60-14 or 60-18 = 5
AHP60-26 or 60-32 = 6
AHP60-50 = 7
AHP60-70 = 8
• LPB network
menu
Number of the appliance
Appliance address (6600)
2
Number of the segment (preset)
Segment address (6601)
0
Adjust the clock rate (preset)
Clock operation (6640)
Slave without adjustment
H. HYDRAULIC VALIDATION
"
Switch the power to the Ecomod back on:
It is necessary to adjust the flow rate of each HP taking the following characteristics into consideration:
Unit flow characteristics of each HP, when all HPs are in operation
AHP60-14
AHP60-18
AHP60-26
AHP60-32
AHP60-50
AHP60-70
Nominal
flow rate
(m³/h)
2.4
3.1
4.5
5.5
8.6
11.5
Refer to § 10 , page 81 for the regulator input/output tests.