05.10.2022
Page 23 / 86
Ecomod Heat Pump Control -
Installation and Servicing
4.6. Settings
Depending on the functions commanded, there are different levels of access to the
settings There are 3 access levels:
U: End user
M: Commissioning (reception, starting up),
S: Specialist (technical level).
4.6.1. “End user” level parameter settings
The “end user” level configuration mode is
accessed from the standard display by pressing
the OK key.
The “PROG” pictogram and the first two sections
are displayed on the screen.
The setting knob is used to scroll through the list
of parameters. Once the parameter to be modified
has been reached, press OK. The parameter
values flashes. Adjust this value using the knob.
The new value is validated by pressing OK.
4.6.2. "Commissioning" and "Specialist” level parameter settings
From the standard display, the "Commissioning" and "Specialist" parameter setting
modes are accessed by pressing the OK button then the information key
for 5
seconds.
Use the knob to go to the desired level:
Commissioning
or
Specialist
then validate your
choice with OK.
The
Commissioning
access level includes the
End user
level. In the same way, the
Specialist
level integrates the
Commissioning
level.
4.6.3. Adjusting the various parameters
From the main menu, after reaching the desired level:
•
Turn the knob to scroll through the menu.
• When the desired menu is displayed, press OK to validate.
•
Turn the knob to adjust the setting.
•
Press OK to confirm the setting
If no setting is made for 8 minutes, the screen returns automatically to the basic display.