Ecomod Heat Pump Control  -  

Installation and Servicing 

OK

Diagrams: 

HYF210

page 5 / 6

G.  SPECIFIC START-UP PROCEDURE

 

"

Make the accessories' electrical connections.

 

"

Start up each HP.

 

"

Perform the following settings in "Specialist" mode:

OK

 Short press

Press 3 seconds               End user        Commissioning       Specialist         OEM

Heat Pump No. 1 Cascade master:

Line No. 

Value

•  Time and date

 menu

Set the time

Hour / minute (1)

HH.MM

Set the date

Day / month (2)

DD.MM

Set the year

Year (3)

YYYY

•  Configuration

 menu

Preset the model of heating heat pump

 Preset (5700) AHP60-14 or 60-18 = 5

AHP60-26 or 60-32 = 6

AHP60-50 = 7

AHP60-70 = 8

Configure the hydraulic station output (preset)

 Relay output QX3 (5892)

DHW pump/valve Q3

Configure the alarm output (preset)

 Relay output QX4 (5830) Alarm output K10

Assign the tank flow sensor (preset)

 

 Sensor input BX3  (5932) B10 line output sensor

Assign the DHW preheating sensor (preset)

Sensor BX4 output (5933) DHW source B3

Configure the H1 input (preset)

H1 input function (5950)

Switching of heating circuit 
+ DHW operation

Configure the contact direction (preset)

Contact H1 action direction (5951)

Normally closed

Configure the H3 input (preset)

H3 input function (5960) Error/alarm message

Configure the contact direction (preset)

Contact H3 action direction (5961) Operation

Configure mixer unit 1 (preset)

Mixer unit 1 function (6014) Multifunction

•  DHW

 menu

Adjust the comfort setting

Nominal setting

 (1610)

- - -°C

•  DHW Tank

 menu

Set the DHW over-value 

(preset)

Flow setpoint over-value (5020)

5°C

•  Timer programme 4/DHW

 menu

Preselection

Preselection (560) Monday-Sunday

Adjust the timer programming

1st phase ON (561) 00: 00 h

Adjust the timer programming

1st phase Off (562) 06: 00 h

Содержание ECOMOD HEAT PUMP CONTROL

Страница 1: ...peci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature for speci cation and maintenance practices visi...

Страница 2: ...Page 2 86 00U07310090 A Ecomod Heat Pump Control Installation and Servicing DECLARATION DE CONFORMITE AUX NIVEAUX D EMIS DECLARATION DE CONFORMITE AUX NIVEAUX D EMIS SION NOX ET CO SION NOX ET CO...

Страница 3: ...NTERFACE 18 4 1 Presentation of the interface 18 4 2 Display 18 4 3 Fault display 20 4 4 Ecomod HMI browsing 21 4 6 Settings 23 5 OPERATING CYCLES 24 5 1 Heat Pump start up 24 5 2 Heat pump shutdown 2...

Страница 4: ...and Servicing 9 HYDRAULIC DIAGRAMS AND CONFIGURATIONS 53 9 1 Symbols used in the diagrams 53 9 2 List of diagrams 54 10 ELECTRICAL VALIDATION 77 12 SPARE PARTS LIST 78 11 LACK OF WATER SAFETY FUNCTIO...

Страница 5: ...ion to comments CAUTION Failure to follow these instructions may cause damage to the installation or to other objects WARNING Failure to comply with these instructions may cause injury and serious dam...

Страница 6: ...ring Regulations CAUTION Before opening the Ecomod Heat Pump Control regulator unit make sure that no water is present on the top of the case CAUTION The control panel is classified as an appliance wh...

Страница 7: ...el is used to control the heat pump and the hydraulic station In this way it is possible to produce domestic hot water according to the Ecomod Heat Pump Control operating mode For further information...

Страница 8: ...eat Pump Control Installation and Servicing figure 2 Dimensions in mm Version with mounting feet 2 3 Delivered unit Case Servicing installation and maintenance instructions Wiring diagram Locking key...

Страница 9: ...level II Protection index Class I surge voltage 800 V Electrical consumption On standby 10W When in operation Depends on appliances plugged in pumps mixing valves Relative humidity 95 Terminal output...

Страница 10: ...lator is protected with a 6 3 A fuse The total load of the consuming elements connected to this regulator must not be more than 6 3 A INFORMATION The electrical connection diagrams temperature sensors...

Страница 11: ...and remove the door by removing the hinge pins shown in figure 6 from the outside Attach the mounting feet using the four screws supplied in the bag Refit the door by proceeding as for removal but in...

Страница 12: ...the tank or bottle in the opening located in the upper section on a bottle 100mm immersion sleeve to be placed in the upper opening at 90 from the flow opening on a primary water tank 160mm immersion...

Страница 13: ...out electrical connections in particular connection to the main supply when all other fitting and installation work is completed WARNING Installations carried out by the customer cable runs gas or fue...

Страница 14: ...Page 14 86 00U07310090 A Ecomod Heat Pump Control Installation and Servicing 3 3 2 Ecomod Heat Pump Control wiring diagram figure 11 Ecomod Heat Pump Control wiring diagram On Off...

Страница 15: ...similar qualification to avoid any danger Tow presses must be tightened tightly enough to withstand cable traction up to 60N CAUTION The Ecomod Heat Pump Control must be powered by special protected...

Страница 16: ...nnection of W3100 hydraulic station with H1 M R1 NO and Com respectively and H3 M R2 NO and Com respectively G Connection of Rubis E1 H Connection of the HP s alarm summary relay output and the hydrau...

Страница 17: ...N Ensure each cable gland is tight so that no connection inside the control panel can be attempted 3 3 6 Changing the Fuse figure 15 Fuse slot Set the switches to Off Switch off the electric power sup...

Страница 18: ...of the interface The Ecomod Heat Pump Control controller user interface comprises An On Off switch An Ecomod system fault summary indicator light whether alone or cascaded A back lit LCD display Two f...

Страница 19: ...parameter settings screen 5 seconds Start up Installer OEM with code 4 2 2 Ecomod HMI preset standard browser display The basic display of the Ecomod Heat Pump Control in DHW pre heating mode includes...

Страница 20: ...his type of fault does not cause operation to be blocked requiring manual intervention Once the source of the fault has been removed the bell disappears automatically When a fault causes the heat pump...

Страница 21: ...at Pump Control Installation and Servicing 4 4 Ecomod HMI browsing Only if fault in progress Only if USB drive detected with suitable files OH2 available only on Ecomod AHP60 50 or 70kW U user S Speci...

Страница 22: ...tatus From the basic display you can scroll basic heat pump information see list below Access Setting Exit ESC 1 HP status 2 DHW status 3 Outdoor temperature 4 DHW temperature 5 Heat pump return tempe...

Страница 23: ...value using the knob The new value is validated by pressing OK 4 6 2 Commissioning and Specialist level parameter settings From the standard display the Commissioning and Specialist parameter setting...

Страница 24: ...down cycle is applied Ecomod Heat Pump Control display Ecomod display Pump and compressor running Pump running Standby state Note The system always applied a minimum 5 minute stop time before restarti...

Страница 25: ...in the maintenance menu YES 134 YES Heat pump alarm Ecomod fault summaries Check the status and presence of a fault on the Ecomod HMI NO 174 YES Hydraulic station error Note the error code on the W31...

Страница 26: ...e 7 The heat pump start up counter has reached the limit set for preventive maintenance 8 Compressor start up frequency is too high analyse the malfunction Acknowledgement of this error message is pre...

Страница 27: ...bbon cables and the accessories connected to CL CL G Navipass Modbus Operation button is locked in stand by Cannot select the heating circuit or hot water mode from the front panel buttons Cannot cont...

Страница 28: ...Sensor input BX1 S 8 5 2 page 40 5932 Sensor input BX3 S 8 5 1 1 page 39 Line No Programming Access See subsection page 5933 Sensor input BX4 S 8 5 1 1 page 39 5950 H1 input function S 8 5 1 1 page 3...

Страница 29: ...1 page 52 8127 Generator 14 status 8 11 1 page 52 8128 Generator 15 priority 8 11 1 page 52 8129 Generator 15 status 8 11 1 page 52 8130 Generator 16 priority 8 11 1 page 52 Line No Programming Access...

Страница 30: ...es The time changes automatically at 2 am winter time to 3 am summer time or from 3 am summer time to 2 am winter time on the first Sunday after the respective dates 8 1 2 User interface Line no Progr...

Страница 31: ...programming level To do this press the OK and ESC buttons together for at least 3 seconds The programming locking function temporary suspension remains effective until the user quits the programming l...

Страница 32: ...0 563 2nd period start time 00 00 24 00 564 2nd period stop time 00 00 24 00 565 3rd period start time 00 00 24 00 566 3rd period stop time 00 00 24 00 576 Default values No Yes The Ecomod Heat Pump C...

Страница 33: ...nd 06 00 the next day If no setting is made for 8 minutes the screen returns automatically to the basic display INFORMATION Every time the user accesses the DHW timer programme 4 menu the first parame...

Страница 34: ...DHW and DHW tank menus when a sensor is connected to its B3 input The control adjusts the DHW temperature to the desired setpoint according to the timer programme 8 2 1 Basic settings 8 2 1 1 Setpoin...

Страница 35: ...rameters and the diagram below describe the DHW charge regulation Line no Programming Possible values 5008 DHW start of charge delay 0 30 min This parameter allows the heat production provided by the...

Страница 36: ...etpoint In order to correctly define the starting point for this gradual setpoint the Ecomod generator is released at its minimum modulation and the plate exchanger is released In this way temperature...

Страница 37: ...rm function on each controller INFORMATION The QX4 output must be a summary of installation faults that includes the hydraulic station It is not possible to distinguish between faults from specific Ec...

Страница 38: ...5894 Relay output QX4 Alarm output K10 Alarm output K10 Alarm output K10 Alarm output K10 5932 Sensor input BX3 B10 line output sensor B10 line output sensor B10 line output sensor B10 line output se...

Страница 39: ...circuit pump 1 Q15 Function not available Alarm output K10 If a fault occurs it is reported by the alarm relay Contact closure has a two minute delay time Once the error is eliminated i e the error m...

Страница 40: ...or 1 Special temp sensor 2 Outdoor sensor B9 Room thermostat B5 Room thermostat B52 Room thermostat B53 The output settings assign the corresponding functions based on the selection None No function o...

Страница 41: ...n is active at input H3 The input causes a regulator error message If the alarm output is configured accordingly relay outputs QX4 line 584 then the error is forwarded or displayed by an additional co...

Страница 42: ...the regulator has already been running for at least two hours If a sensor fails after registration then the standard device generates an error message This setting is used to immediately register the...

Страница 43: ...tem time by the master The regulator time is however automatically and constantly adapted to match system Master The time can be set on the regulator The regulator time becomes the reference time for...

Страница 44: ...amming Possible values 6700 In progress 00 00 23 59 h m 8 7 2 History Line no Programming Possible values 6800 6802 6804 6806 6808 6810 6812 6814 6816 6818 History 00 00 23 59 h m The unit stores the...

Страница 45: ...eriod of time in months since the last service check If the value is over the Heat pump interval setting Heat pump maintenance The symbol is displayed and A maintenance message is provided at the info...

Страница 46: ...ssor does not come back on automatically if the heat pump reaches a safety limit value during the active commissioning process In this case the output selection is reset 7207 0 but the commissioning f...

Страница 47: ...tput QX3 Relay output QX4 Relay output Q5 Relay output QX21 module 1 Relay output QX22 module 1 Relay output QX23 module 1 Relay output QX21 module 2 Relay output QX22 module 2 Relay output QX23 modul...

Страница 48: ...2 H3 Line no Programming Possible values 7840 H1 voltage signal 0 10 V 7841 H1 contact status Open Closed 7845 Module 1 H2 voltage signal 0 10 V 7846 Module 1 H2 contact status Open Closed 7848 Module...

Страница 49: ...locked 81 Load locking active 82 Forcing maximum temperature of the tank 83 Forcing maximum temperature of load 84 Forcing anti Legionella setpoint 85 Forcing comfort setpoint 86 Forced load active 67...

Страница 50: ...um active compr stop time 35 Time limit active 37 Maximum active compr stop time 38 Compressor EN 46 Heating mode 137 Locked max return temperature 261 Locked min return temperature 262 Locked max flo...

Страница 51: ...aration activated Out Temp limitation active Not released Released 8138 Cascade starting temperature 0 140 C 8139 Cascade starting setpoint 0 140 C 8140 Cascade return temperature 0 140 C 8150 Current...

Страница 52: ...mperature 2 B31 0 140 C 8840 Number of DHW pump hours 0 8333 7 00h 8841 DHW pump starts counter 0 199999 8950 Line start temperature 0 140 C 8951 Line start setpoint temperature 0 140 C 9016 Special t...

Страница 53: ...stallation is used the flow must be balanced between all units We recommend performing this balancing using balancing valves so that individual flow levels can be measured over time CAUTION Flow adjus...

Страница 54: ...ttle or tank 1 DHW pre heating tank Heat Pump only with two Pre Heating Tanks 60 2 or 3 DHW preheating tanks 2 or 3 Heat Pumps Cascade with one Pre Heating Tank 65 1 decoupling bottle or tank 1 DHW pr...

Страница 55: ...one Pre Heating Tank 1 decoupling bottle or tank 1 DHW pre heating tank Diagrams HYF110 HYF111 page 1 5 A HYDRAULIC DIAGRAM figure 16 Diagram HYF110 figure 17 Diagram HYF111 B REGULATION ACCESSORIES...

Страница 56: ...duration Care will be taken to ensure that draw offs are virtually non existent during this time period This was defined during the sizing study If it is deemed necessary to implement anti Legionella...

Страница 57: ...roller terminals H1 M Diagrams HYF110 HYF111 page 3 5 E HYDRAULIC STATION F HYDRAULIC STATION PROGRAMMING Start up the hydraulic station INFORMATION The hydraulic station arrives pre programmed and re...

Страница 58: ...re the hydraulic station output preset Relay output QX3 5892 DHW pump valve Q3 Configure the alarm output preset Relay output QX4 5830 Alarm output K10 Assign the tank flow sensor preset Sensor input...

Страница 59: ...the timer programming 1st phase Off 562 06 00 h Adjust the timer programming 2nd phase ON 563 22 00 h Adjust the timer programming 2nd phase Off 564 24 00 h Switch the DHW rate to automatic H HYDRAULI...

Страница 60: ...taken to ensure that draw offs are virtually non existent during this time period This was defined during the sizing study If it is deemed necessary to implement anti Legionella cycles on the downstr...

Страница 61: ...aulic station Terminal block Heat pump A B Ref Diagrams HYF120 page 2 5 When 2 or more DHW preheating tanks are linked to the HP it is necessary to add an isolation valve at the plate exchanger s seco...

Страница 62: ...troller terminals H1 M Diagrams HYF120 page 3 5 E HYDRAULIC STATION F HYDRAULIC STATION PROGRAMMING Start up the hydraulic station INFORMATION The hydraulic station arrives pre programmed and requires...

Страница 63: ...elay output QX4 5830 Alarm output K10 Assign the tank flow sensor preset Sensor input BX3 5932 B10 line output sensor Assign the DHW preheating sensor pre set Sensor BX4 output 5933 DHW source B3 Conf...

Страница 64: ...ramming 2nd phase Off 564 24 00 h Switch the DHW rate to automatic H HYDRAULIC VALIDATION Switch the power to the Ecomod back on It is necessary to adjust the flow rate of the HPtaking the following c...

Страница 65: ...h one Pre Heating Tank 1 decoupling bottle or tank 1 DHW pre heating tank Diagrams HYF210 page 1 6 A HYDRAULIC DIAGRAMS figure 19 Diagram HYF210 B REGULATION ACCESSORIES REQUIRED Quantity Appliance re...

Страница 66: ...s the solution shown does not contain the hydraulic or electrical elements used to perform them If this is to be expected please contact our pre sales department to choose the most suitable solution f...

Страница 67: ...05 10 2022 Page 67 86 Ecomod Heat Pump Control Installation and Servicing Diagrams HYF210 page 3 6 Heat Pump No 2 Terminal block Heat pump A B Ref MB DB OCI 345 Controller No 1...

Страница 68: ...terminals QX3 FX3 Controller No 1 terminals H3 M Controller No 1 terminals H1 M F HYDRAULIC STATION PROGRAMMING Start up the hydraulic station INFORMATION The hydraulic station arrives pre programmed...

Страница 69: ...y output QX4 5830 Alarm output K10 Assign the tank flow sensor preset Sensor input BX3 5932 B10 line output sensor Assign the DHW preheating sensor preset Sensor BX4 output 5933 DHW source B3 Configur...

Страница 70: ...ng heat pump Preset 5700 AHP60 14 or 60 18 5 AHP60 26 or 60 32 6 AHP60 50 7 AHP60 70 8 LPB network menu Number of the appliance Appliance address 6600 2 Number of the segment preset Segment address 66...

Страница 71: ...SORIES REQUIRED Quantity Appliance reference Order No OCI kit 1 per heat pump OCI 345 AH059752 Immersion sleeve sensor kit 2 QAZ 36 AH059261 2 Heat Pumps Cascade with 2 or 3 Pre Heating Tanks 1 decoup...

Страница 72: ...artment to choose the most suitable solution for your installation It should also be noted that the gas back up is sized to fulfil all DHW requirements on its own This is an additional safety mechanis...

Страница 73: ...05 10 2022 Page 73 86 Ecomod Heat Pump Control Installation and Servicing Diagrams HYF220 HYF23a page 3 6 Heat Pump No 2 Terminal block Heat pump A B Ref MB DB OCI 345 Controller No 1...

Страница 74: ...erminals QX3 FX3 2WV tank Controller No 1 terminals H3 M Controller No 1 terminals H1 M F HYDRAULIC STATION PROGRAMMING Start up the hydraulic station INFORMATION The hydraulic station arrives pre pro...

Страница 75: ...n output preset Relay output QX3 5892 DHW pump valve Q3 Configure the alarm output preset Relay output QX4 5830 Alarm output K10 Assign the tank flow sensor preset Sensor input BX3 5932 B10 line outpu...

Страница 76: ...to automatic Heat Pump No 2 Line No Value Configuration menu Preset the model of heating heat pump Preset 5700 AHP60 14 or 60 18 5 AHP60 26 or 60 32 6 AHP60 50 7 AHP60 70 8 LPB network menu Number of...

Страница 77: ...output Relay test 7700 Output QX3 Cancel enable Relay test 7700 No test Generator diagnostics menu Check the values for the heat pump in use Heat pump flow sensor Heat pump flow temperature 8412 C Hea...

Страница 78: ...icator light AH79691 010 Ecomod Heat Pump Control switch cover AH79694 011 Ecomod Heat Pump Control wall mounting AH79690 Ecomod Heat Pump Control x84 x86 connectors AH79698 Complete wiring set with E...

Страница 79: ...05 10 2022 Page 79 86 Ecomod Heat Pump Control Installation and Servicing figure 22 Ecomod Heat Pump Control set 001 011 002 007 005 006 008 003 010 009 004...

Страница 80: ...ith the control panel to be ordered separately as acces sories 2 QAZ36 immersion sensors CTN 10 k 25 C Ref AH059261 Install the sensor in the sensor immersion sleeve Bulb length 40 5 mm diameter 6 mm...

Страница 81: ...827 47 0 451 20 0 7 578 3 0 3 279 14 0 1 555 31 0 796 48 0 436 19 0 7 193 2 0 3 131 15 0 1 492 32 0 767 49 0 421 18 0 6 831 1 0 2 990 16 0 1 433 33 0 740 50 0 407 17 0 6 489 0 0 2 857 17 0 1 375 34 0...

Страница 82: ...Page 82 86 00U07310090 A Ecomod Heat Pump Control Installation and Servicing...

Страница 83: ...ommunication bus connected to its controller regulation Yes No Primary hydraulic circuit Hydraulics performed according to the diagram provided in the study Yes No Fluid conveyed Water Water Glycol Co...

Страница 84: ...ance with HP power cable sections Yes No Check that connections are tight Done Pre operations With the disconnect switch open please open the fuse holders contained in the HP then close the HP s main...

Страница 85: ...05 10 2022 Page 85 86 Ecomod Heat Pump Control Installation and Servicing...

Страница 86: ...2 Ideal is a trademark of Ideal Boilers Registered Office Ideal Boilers Ltd PO Box 103 National Avenue Kingston Upon Hull HU5 4JN Tel 01482 492251 Fax 01482 448858 Registration No London 322 137 Ideal...

Отзывы: