Ecomod Heat Pump Control -
Installation and Servicing
8.6.3. Clock*
Line
no.
Programming
Possible values
6640
Clock operation
Independent | Slave without
adjustment | Slave with
adjustment | Master
This setting determines the action of the system time on the time set in the regulator.
Independent
The time can be set on the regulator. The regulator time is not synchronised with system
time.
Slave without adjustment
The time cannot be set on the regulator. The regulator time is automatically synchronised
with system time all of the time.
Slave with adjustment
The time can be set on the regulator. It is simultaneously taken as the system time
by the master. The regulator time is however automatically and constantly adapted to
match system.
Master
The time can be set on the regulator. The regulator time becomes the reference time
for the system. System time is synchronised.
* = restricted access leve
l
8.6.1. LPB address*
Line
no.
Programming
Possible values
6600
Appliance address
0 … 16
6601
Segment address
0 ... 14
The device address identifies every device on the bus, in a similar way to a postal
address. Every device must have a correct address to ensure communication.
Prefer
segment 0 for generators.
8.6.2. System messages*
Line
no.
Programming
Possible values
6612
Alarm timeout
0 ... 60 min
Timeout between when the fault appears and when the output set as the "K10 alarm
output" is triggered.
This time also acts when sending the fault condition for a slave heat pump to the master
heat pump.