Page 48 / 86
00U07310090-A
Ecomod Heat Pump Control -
Installation and Servicing
8.9.2. Sensor input test
Line
no.
Programming
Possible values
7804
Sensor T° BX1
-28 … 350°C
7806
Sensor T° BX3
-28 … 350°C
7807
Sensor T° BX4
-28 … 350°C
The input test is used to read the current measurement values from the device input
terminals. This is used to quickly check the wiring.
8.9.3. Test of inputs H1 / H2 / H3*
Line
no.
Programming
Possible values
7840
H1 voltage signal
0 … 10 V
7841
H1 contact status
Open | Closed
7845
Module 1 H2 voltage signal
0 … 10 V
7846
Module 1 H2 contact status
Open | Closed
7848
Module 2 H2 voltage signal
0 … 10 V
7849
Module 2 H2 contact status
Open | Closed
7851
Module 3 H2 voltage signal
0 … 10 V
7852
Module 3 H2 contact status
Open | Closed
7854
H3 voltage signal
0 … 10 V
7855
H3 contact status
Open | Closed
The input test is used to read the current measurement values from the device input
terminals. This is used to quickly check the wiring.
* = restricted access leve
l