Page 30 / 86
00U07310090-A
Ecomod Heat Pump Control -
Installation and Servicing
8. PARAMETERS
8.1. "User interface" parameters
8.1.1. Time setting
Line
no.
Programming
Possible values
1
Hours / minutes
00:00 … 23:59
2
Day / month
01:01… 31.12
3
Year
1900 … 2099
5
Start of summer time
01:01… 31.12
6
End of summer time
01:01… 31.12
The controller is provided with a yearly clock that displays the time, day and date.
So that the programming sequences can operate properly, the time and the date must
be correctly set on the clock.
N.B: Toggling between summer and winter time
Dates have been programmed for the change between summer and winter times. The
time changes automatically at 2 am (winter time) to 3 am (summer time) or from 3 am
(summer time) to 2 am (winter time) on the first Sunday after the respective dates.
8.1.2. User interface
Line
no.
Programming
Possible values
20
Language
English | Deutsch | Français |
Italiano | Nederlands | Español
22
Temporary
temporary | permanent
26
Operation locking
stop | start
27
Programming locking
stop | start
28
Direct adjustment
Automatic storage | Storage
with confirmation
29
Units
°C, bar | °F, PSI
Info. (22):
• Temporary:
After pressing the "Infos" button, the display returns to the basic "preset" display
after eight minutes or by pressing the Operating modes button.
• Permanent:
After pressing the "Infos" button, the display returns to the "new" standard display
after a maximum of eight minutes. The last information selected is visible on the
new basic display.