Ecomod Heat Pump Control -
Installation and Servicing
OK
Diagrams: HYF110 - HYF111
page 4 / 5
G. SPECIFIC START-UP PROCEDURE
"
Make the accessories' electrical connections.
"
Start up the HP on its own.
"
Perform the following settings in "Specialist" mode:
OK
Short press
Press 3 seconds End user Commissioning Specialist OEM
Line No.
Value
• Time and date
menu
Set the time
Hour / minute (1)
HH.MM
Set the date
Day / month (2)
DD.MM
Set the year
Year (3)
YYYY
• Configuration
menu
Preset the model of heating heat pump
Preset (5700) AHP60-14 or 60-18 = 5
AHP60-26 or 60-32 = 6
AHP60-50 = 7
AHP60-70 = 8
Configure the hydraulic station output (preset)
Relay output QX3 (5892)
DHW pump/valve Q3
Configure the alarm output (preset)
Relay output QX4 (5830) Alarm output K10
Assign the tank flow sensor (preset)
Sensor input BX3 (5932) B10 line output sensor
Assign the DHW preheating sensor (preset)
Sensor BX4 output (5933) DHW source B3
Configure the H1 input (preset)
H1 input function (5950)
Switching of heating circuit
+ DHW operation
Configure the contact direction (preset)
Contact H1 action direction (5951)
Normally closed
Configure the H3 input (preset)
H3 input function (5960) Error/alarm message
Configure the contact direction (preset)
Contact H3 action direction (5961) Operation
Configure mixer unit 1 (preset)
Mixer unit 1 function (6014) Multifunction
• DHW
menu
Adjust the comfort setting
Nominal setting
(1610)
- - -°C
• DHW Tank
menu