Ecomod Heat Pump Control -
Installation and Servicing
8.5.2.4. Register sensor*
If faulty sensors are detected after installation and to avoid integrating them with correct
status (which may occur if automatic detection is used), there is a Commissioning
function.
This function learns to recognise the connected sensors and, if a fault occurs, generates
an error message while inhibiting any installation diagram change.
Line
no.
Programming
Possible values
6200
Register sensor
no | yes
At midnight, the standard device records the status of the sensor terminals, so long
as the regulator has already been running for at least two hours. If a sensor fails after
registration, then the standard device generates an error message. This setting is used
to immediately register the sensors. This may be necessary, e.g. when a sensor is
removed and is no longer of any use.
Line
no.
Programming
Possible values
6205
Reset parameters
no | yes
All of the parameters can be reset to the factory settings except for the following pages:
• Time and date
• User interface
• Radio and all time programmes, and
• And the manual rate setpoint.
* = restricted access leve
l
8.6. "LPB system" parameters
To communicate with other regulators, OCI 345 offers an LPB bus.
This accessory screws onto the heat pump controller unit.
The LPB bus allows the Ecomod Heat Pump Control regulation to create HP cascades.