![Ideal Heating ECOMOD HEAT PUMP CONTROL Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/ideal-heating/ecomod-heat-pump-control/ecomod-heat-pump-control_installation-and-servicing_3612612038.webp)
Page 38 / 86
00U07310090-A
Ecomod Heat Pump Control -
Installation and Servicing
8.5.1. Hydraulic configuration
8.5.1.1. Assigning the Ecomod model and the application*
Line
no.
Programming
5700
Preselect
This parameter is used to preset a number of values that ensure a match between
the Ecomod Heat Pump Control heating or hot water application and the model of the
Ecomod used in the installation.
Line
no.
Function
5
Ecomod
AHP60 14 18kW
6
Ecomod
AHP60 26 32kW
7
Ecomod
AHP60 50kW
8
Ecomod
AHP60 70kW
5892
Relay output QX3
DHW pump/valve
Q3
DHW pump/valve
Q3
DHW pump/valve
Q3
DHW pump/valve
Q3
5894
Relay output QX4
Alarm output K10
Alarm output K10
Alarm output K10
Alarm output K10
5932
Sensor input BX3
B10 line output
sensor
B10 line output
sensor
B10 line output
sensor
B10 line output
sensor
5933
Sensor input BX4
DHW sensor B3
DHW sensor B3
DHW sensor B3
DHW sensor B3
5950
H1 input function
Switching of
heating c
DHW operation
Switching of
heating c
DHW operation
Switching of
heating c
DHW operation
Switching of
heating c
DHW operation
5951
H1 input function
action direction
Normally closed
Normally closed
Normally closed
Normally closed
5960
H3 input function
Error/alarm
message
Error/alarm
message
Error/alarm
message
Error/alarm
message
5961
H3 input function
action direction
Operation
Operation
Operation
Operation
* = restricted access leve
l