Ensure for Grade 3 or 4 compliant systems, the minimum PIN length is set for 6 digits.
⦁
To comply with EN 50131-1 Engineer access must first be authorized by a user, therefore Installer codes will
only be accepted when the system is unset. If additional restriction is required then Engineer access may be
time limited to the first 30 seconds after the system is unset.
⦁
Reporting delay –Violation off the entry path during the entry delay countdown will trigger a warning
alarm. The warning alarm should not cause a main alarm signal and is not reported at this time. It can be
signaled locally, visually and or by internal siren type. If the area is not disarmed within 30 seconds, the
entry delay has expired or another instant input is violated, the main alarm will be triggered and reported.
⦁
To comply with EN 50131-1 neither Internals Only on Part Set Input Alarm nor Internals Only on Part Set
Tamper Alarm should be selected.
⦁
To comply with EN 50131-1 Single Button Setting should not be selected.
⦁
To comply with EN 50131-1 only one battery can be connected and monitored per system. If more capacity is
required a single larger battery must be used.
Anti Masking
To comply with EN 50131-1 Grade 3 or 4 for Anti Masking, detectors with a separate or independent mask signal
should be used and the mask output should be connected to another input.
I.e. Use 2 inputs per detector. One input for alarm/tamper and one input for masking.
To comply with EN 50131-1:
⦁
Do not fit more than 10 unpowered detectors per input,
⦁
Do not fit more than one non-latching powered detector per input,
⦁
Do not mix unpowered detectors and non-latching powered detectors on an input.
To comply with EN 50131-1 the Entry Timer should not be programmed to more than 45 seconds.
To comply with EN 50131-1 the Bell Cut-Off Time should be programmed between 02 and 15 minutes.
EN 50131-1 requires that detector activation LEDs shall only be enabled during Walk Test. This is most
conveniently achieved by using detectors with a Remote LED Disable input.
PRT-IPIC-POE-C | Vandal Resistant VoIP Intercom with Camera | Installation Manual
53