ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
261
Yearly
Accumulated
Electricity
SA + 300134
2
Float
Floating Point
[3x] Input Register, Unit : Register(16 Bits)
Power Meter Type
PM_SA + 300000
1
Int16
2133
Reserved
PM_SA + 300001
1
-
Reserved
Reserved
PM_SA + 300002
1
-
Reserved
Firmware Version
PM_SA + 300003
1
BCD
0x0100~
Address
PM_SA + 300004
1
UInt16 1~247
Error Code
PM_SA + 300005
1
UInt16
-1=Initializing
0=Failed
1=Success
Reserved
PM_SA + 300011
1
-
Reserved
PT Ratio
PM_SA + 300012
2
Float
0.01~655.35
CTRatio
PM_SA + 300014
2
Float
1~65535
PM-2134
Parameter Name
Modbus
Address
Length
Data
Type
Range
[3x]Input Register, Unit : Register(16 Bits)
CT
1
V
SA + 300000
2
Float
Floating Point
I
SA + 300002
2
Float
Floating Point
kW
SA + 300004
2
Float
Floating Point
kvar
SA + 300006
2
Float
Floating Point
kVA
SA + 300008
2
Float
Floating Point
PF
SA + 300010
2
Float
Floating Point
kWh
SA + 300012
2
Float
Floating Point
kvarh
SA + 300014
2
Float
Floating Point
kVAh
SA + 300016
2
Float
Floating Point
CT
2
V
SA + 300018
2
Float
Floating Point
I
SA + 300020
2
Float
Floating Point
kW
SA + 300022
2
Float
Floating Point
kvar
SA + 300024
2
Float
Floating Point
kVA
SA + 300026
2
Float
Floating Point
PF
SA + 300028
2
Float
Floating Point
kWh
SA + 300030
2
Float
Floating Point
Содержание PMC-523 Series
Страница 1: ...ICP DAS PMC 523x PMC 224x PMD Power Meter Concentrator Series User Manual Version 3 2 4...
Страница 54: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 39 Figure5 32 Energy Usage Breakdown by Circuit Group Chart...
Страница 165: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 150 Figure9 14 The Import of MQTT Topic...
Страница 205: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 190 Figure10 53 PUE Setting Page 2...