ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
269
PM-3112
、
PM-3112-MTCP (2 Loops 1 Phase)
Parameter Name
Modbus
Address
Length
Data
Type
Range
[0x] Coils Output, Unit : Coil(8 Bits)
DO Ch.0
SA + 000000
1
Byte
0=OFF, 1=ON
DO Ch.1
SA + 000001
1
Byte
0=OFF, 1=ON
[3x] Input Register, Unit : Register(16 Bits)
CT
1
V
SA + 300000
2
Float
Floating Point
I
SA + 300002
2
Float
Floating Point
kW
SA + 300004
2
Float
Floating Point
kvar
SA + 300006
2
Float
Floating Point
kVA
SA + 300008
2
Float
Floating Point
PF
SA + 300010
2
Float
Floating Point
kWh
SA + 300012
2
Float
Floating Point
kvarh
SA + 300014
2
Float
Floating Point
kVAh
SA + 300016
2
Float
Floating Point
CT
2
V
SA + 300018
2
Float
Floating Point
I
SA + 300020
2
Float
Floating Point
kW
SA + 300022
2
Float
Floating Point
kvar
SA + 300024
2
Float
Floating Point
kVA
SA + 300026
2
Float
Floating Point
PF
SA + 300028
2
Float
Floating Point
kWh
SA + 300030
2
Float
Floating Point
kvarh
SA + 300032
2
Float
Floating Point
kVAh
SA + 300034
2
Float
Floating Point
CT
1
15/30/60 mins
Actual Demand
SA + 300036
2
Float
Floating Point
15/30/60 mins
Forecast Demand
SA + 300038
2
Float
Floating Point
Max. Demand
(Hourly)
SA + 300040
2
Float
Floating Point
Max. Demand
(Daily)
SA + 300042
2
Float
Floating Point
Max. Demand
(Monthly)
SA + 300044
2
Float
Floating Point
Daily Accumulated SA + 300046
2
Float
Floating Point
Содержание PMC-523 Series
Страница 1: ...ICP DAS PMC 523x PMC 224x PMD Power Meter Concentrator Series User Manual Version 3 2 4...
Страница 54: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 39 Figure5 32 Energy Usage Breakdown by Circuit Group Chart...
Страница 165: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 150 Figure9 14 The Import of MQTT Topic...
Страница 205: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 190 Figure10 53 PUE Setting Page 2...