background image

ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 

 

 

 

305 

 

The  allocation  of  the  Modbus  Address  in  PMC/PMD  for  the  Discrete  Input 

setting of this Modbus RTU module is shown as below

 

Discrete Input 

Index 

The Modbus Address in 

Modbus RTU Module 

The mapping Modbus 

Address in PMC/PMD   

10000 

1

3400

 

10001 

1

3401

 

10002 

1

3402

 

10003 

1

3403

 

10004 

1

3404

 

10005 

1

3405

 

10006 

1

3406

 

10007 

1

3407

 

10008 

1

3408

 

10 

10009 

1

3409

 

 

 

The  allocation  of  the  Modbus  Address  in  PMC/PMD  for  the  Input  Register 

setting of this Modbus RTU module is shown as below

 

Input Register 

Index 

The Modbus Address in 

Modbus RTU Module 

The mapping Modbus 

Address in PMC/PMD   

30007 

3

3400

 

30009 

3

3402

 

30011 

3

3404

 

30013 

3

3406

 

 

The  allocation  of  the  Modbus  Address  in  PMC/PMD  for  the  Holding  Register 

setting of this Modbus RTU module is shown as below

 

Holding 

Register Index 

The Modbus Address in 

Modbus RTU Module 

The mapping Modbus 

Address in PMC/PMD   

40020 

4

3400

 

40022 

4

3402

 

40024 

4

3404

 

Содержание PMC-523 Series

Страница 1: ...ICP DAS PMC 523x PMC 224x PMD Power Meter Concentrator Series User Manual Version 3 2 4...

Страница 2: ...close or terminate the communication mechanisms of their systems ICP DAS cannot guarantee that this controller is free of any actual or legal defects including but not limited to stability reliability...

Страница 3: ...16 5 1 2 Power Meter Statistics Information Overview 20 5 1 3 Other Information 21 5 1 4 I O Information 21 5 2 Power Data Information 22 5 2 1 Overview 22 5 2 2 Group Overview 23 5 3 Realtime Chart 2...

Страница 4: ...ng 74 7 1 Power Meter Setting 75 7 1 1 Scan to add Modbus RTU Power Meters 76 7 1 2 Add Modbus RTU Power Meter Manually 77 7 1 3 Add Modbus TCP Power Meter Manually 79 7 1 4 Power Meter List Interface...

Страница 5: ...Bluemix Setting 140 9 3 MQTT Setting 142 9 3 1 Broker Setting 142 9 3 2 Topic Import Export Setting 148 10 Advanced Setting 151 10 1 Email Setting 151 10 2 SMS Setting 155 10 2 1 SMS Alarm Setting 155...

Страница 6: ...oft Azure 220 11 2 5 IBM Bluemix 221 11 2 6 MQTT 223 11 2 7 Timer 225 11 2 8 Email 226 11 2 9 SMS Alarm 226 11 2 10 SNMP Trap 227 11 2 11 LINE Notify 228 11 2 12 Messenger 228 11 2 13 Data Logger 229...

Страница 7: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual Appendix VIII PMC PMD Connection setting for IoTstar 329...

Страница 8: ...e4 14 Power data Overview page 14 Figure4 15 Select the classification of Power data 14 Figure4 16 Display power data of the selected classification 15 Figure5 1 Information display options on Main Pa...

Страница 9: ...ure5 33 PUE information Realtime 40 Figure5 34 PUE information History 1 41 Figure5 35 PUE information History 2 41 Figure5 36 I O Information login as Administrator 42 Figure5 37 I O Information logi...

Страница 10: ...up Setting Window 67 Figure6 27 Configurations for Subgroup 67 Figure6 28 Loops Phases of subgroup Setting 68 Figure6 29 Choose Loops Phased of Subgroup 69 Figure6 30 Add Loops Phases for Subgroup 69...

Страница 11: ...nge for the M 7000 DL module 95 Figure7 29 Scanning the M 7000 DL modules 96 Figure7 30 The M 7000 DL List after Scan operation 96 Figure7 31 Select the actual M 7000 DL modules connected to PMC PMD 9...

Страница 12: ...roker 143 Figure9 8 MQTT Broker Parameter setting page 143 Figure9 9 Publish Message and Subscribe Topic setting page 145 Figure9 10 Publish Message Setting Page 146 Figure9 11 Subscribe Topic Setting...

Страница 13: ...on of the Facebook Fan Page is Done 174 Figure10 32 Set up the search for the Fan Page 174 Figure10 33 Publish the QR Code of the Fan Page 175 Figure10 34 Log in the facebook for developers page 177 F...

Страница 14: ...e11 16 Subscribe Topic condition setting 207 Figure11 17 Connection Status condition setting page 208 Figure11 18 Timer condition setting page 208 Figure11 19 Schedule condition setting page 209 Figur...

Страница 15: ...1 40 Timer action setting page 225 Figure11 41 Email action setting page 226 Figure11 42 SMS Alarm action setting page 226 Figure11 43 SNMP Trap Action Setting Page 227 Figure11 44 LINE Notify action...

Страница 16: ...uct Series PMC 523x PMC 224x Hardware Dimension 117 mm x 126 mm x 58 mm 33 mm x 160 mm x 129 mm Number of LAN Port LAN port x 1 LAN port x 2 LCD Detail Model Name PMC 523x PMC 2241 Support Ethernet PM...

Страница 17: ...es and functions such as IF THEN ELSE logic rule execution and LINE Notify Email SMS Alarm Notification PMC 523x PMC 224x PMD offers more thought out power demand management and alarm notification fun...

Страница 18: ...ution for power management and monitoring that makes more efficient energy usage PMC PMD features Web Based Operation No extra software tool is required all operations can be done through the Web brow...

Страница 19: ...to connect with power meters collect and transfer the power data to the Cloud platform for future data analysis PMC 523x PMC 224x PMD also can receive the message which is published from the Cloud pla...

Страница 20: ...meters and I O modules how to display and log the power data how to edit logic of the rules and how to download the rules to the PMC 523x PMC 224x PMD for conditional execution In the following docume...

Страница 21: ...web page go to System Setting Network Setting modify the network setting to fit current network environment More detailed setting information please refer to 6 2 Network Setting 6 Save the settings a...

Страница 22: ...allows performing Logic rule edition Only one administrator is allowed to login into the system at the same time General User Default password User General users are allowed to view power meter data a...

Страница 23: ...page will be displayed and will automatically read settings of the PMC PMD to the webpage Figure4 1 Main Page PMC PMD main page could be divided into 3 areas A System function area B Sub function area...

Страница 24: ...user the setting functions in Rules management toolbar and System function toolbar will be locked and only allows viewing the power meter data the I O module data and Real time system information The...

Страница 25: ...save the new settings cleared settings to the PMC PMD Please note once the settings are cleared and save to the PMC PMD the settings will be cleared permanently Figure4 6 Confirm to clear settings Loa...

Страница 26: ...0 Confirm to logout The settings are not saved Please note 1 All the edited settings on the webpage have to be saved to PMC PMD to make all settings take effect before click on button the settings wil...

Страница 27: ...pt on the list Figure4 12 Real time information list 4 1 3 System function toolbar According to the level of login permission the System function toolbar will be different If login as an administrator...

Страница 28: ...isplayed to show the current function path Figure4 13 Current function path 4 3 Data review System setting area Data review System setting area allows to set system parameters and data review of PMC P...

Страница 29: ...data immediately The power data classification includes the following options V Voltage I Current kW Real Power kvar Reactive Power kVA Apparent Power PF Power Factor kWh kvarh kVAh Daily Accumulated...

Страница 30: ...ries User Manual 15 Figure4 16 Display power data of the selected classification Connection Status will reveal the connection status between the power meter and PMC PMD the graphic indicators are as f...

Страница 31: ...able Information and UID information shown as follow Figure5 1 Information display options on Main Page 5 1 Power Meter Information Power Meter Information page displays detailed power data informatio...

Страница 32: ...er Attribute The Power Meter Attribute section will display different information according to different power meters and the ways they are connected to the PMC PMD Currently PMC PMD supports connecti...

Страница 33: ...es real time power data information of the selected Power Meter For 3 phase power meter it will display real time information of Phase A Phase B and Phase C Figure 5 5 For single phase power meter it...

Страница 34: ...n of PM 3112 Reset Accumulated Value of the Power Meter When login as the Administrator it allows to click on Reset to reset the value of kWh kvarh and kVAh to be 0 if required Please Note After perfo...

Страница 35: ...and and Monthly Maximum Demand etc In the Statistics Information section the Daily Monthly Yearly Accumulated Electricity and Daily Monthly Yearly Carbon Emissions for each loop will be displayed Figu...

Страница 36: ...fic parameters of the power meter Figure5 9 Power Meter Other Information Page 5 1 4 I O Information In the I O information page the I O status of the power meter will be listed When login as the Admi...

Страница 37: ...ification from the dropdown list of the Data Classification field it will list the requested data from various power meters for easy comparison The page refreshes every 20 seconds the user could also...

Страница 38: ...5 2 2 Group Overview Power Data Information group overview mode allows display of power data of pre set group of power meters please refer to 6 7 Power Meter Group Setting The page refreshes every 20...

Страница 39: ...splayed power data will be varied according to the selected power data classification 5 3 Realtime Chart Realtime Chart allows display of power information of the power meter in real time trend and pi...

Страница 40: ...could choose desired power data classification to view the corresponding Realtime Chart The chart refreshes every 5 seconds Figure5 15 Realtime Chart Power Meter Mode There are three function icons o...

Страница 41: ...the corresponding subgroups will be listed If the selected Group contains no subgroup or the subgroup doesn t setup any loop phase of the power meter the inquiry operation will not be able to perform...

Страница 42: ...ed The user could click and drag on the chart and move forward or backward to show desired time zone Click to resume the update of the chart To view the data on a specific marker move the mouse over t...

Страница 43: ...of the Power Meter List if no power meter is connected the inquiry operation will not be able to perform Data Classification Data Classification allows to inquire various power data options including...

Страница 44: ...ll be displayed Figure5 18 Historical Data Chart for power data On the upper left of the Historical Chart there are 4 function icons Set the Historical Chart to be default status Zoom in the Y axis of...

Страница 45: ...e Go to next page Go to last page 5 5 Historical Data Report The Historical Data Report allows display of the power data report of desired power meter specify the power meter power classification and...

Страница 46: ...eport Monthly Report or Annual Report options Report Date The dates that are available for data retrieval will be displayed Please note if no log file is available the inquiry operation will not be pe...

Страница 47: ...s by Time and Energy Usage Breakdown by Circuit Group The user can query electricity analysis for specific date by selecting Chart Type Data Classification Date and Loop s Phase s the following sectio...

Страница 48: ...Usage KWh and Maximum Demand Chart Type Provides Yearly Chart Monthly Chart and Daily Chart Date Select the date range to be queried the system will provide the date range can be queried Inquiry Mode...

Страница 49: ...Click on Inquiry button to display the trend of Energy Usage Analysis for the specified date range If the selected date does not contain the file or exceeds the date of the file storage range a messa...

Страница 50: ...ut the Y axis of the Energy Usage Analysis by Trend Chart Hide the markers on the Energy Usage Analysis by Trend Chart Show the markers on the Energy Usage Analysis by Trend Chart 5 6 2 Energy Usage A...

Страница 51: ...fication includes V voltage I current PF power factor Energy Usage KWh and Maximum Demand Chart Type Provides Yearly Chart Quarterly Chart and Monthly Chart Date Select the date range to be queried th...

Страница 52: ...ta classification and the time range under this section and then select the loop s phase s to be inquired the corresponding Energy Usage Breakdown by Circuit Group will be displayed in category pie ch...

Страница 53: ...ration Figure5 31 Inquiry by Group Mode User defined In user defined mode all power meters connected to the PMC PMD will be listed If no power meter is connected the user will not be able to perform i...

Страница 54: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 39 Figure5 32 Energy Usage Breakdown by Circuit Group Chart...

Страница 55: ...lues which are calculated by Total Facility Energy and IT Equipment Energy preset by users The page refreshes every 20 seconds the user could also click Refresh button to refresh the data immediately...

Страница 56: ...Provides Daily Chart and Monthly Chart Date The dates which are available for PUE data retrieval will be displayed Please note if no log file is available the inquiry operation will not be performed...

Страница 57: ...he PMC PMD If login as the Administrator it allows to modify the values of Internal Registers or output values of the DO AO channels Figure 5 36 If login as a general user they are allowed to view the...

Страница 58: ...Chart There are three function icons on the upper area of the I O Realtime Chart The icon allows to pause the update of the chart only the data within the 25 minutes will be displayed The user could...

Страница 59: ...ield select the I O channel from the Channel Selector field then click on Inquiry button it will show the chart The interface is shown as below User also can click the Download CSV button to download...

Страница 60: ...t be able to perform Click on Inquiry to display the channel data historical statistic chart Figure 5 40 of the selected date If the selected date does not contain the file or exceeds the date of the...

Страница 61: ...ollowing information The PMC PMD failed to read data of the power meter s Change the network settings on the PMC PMD Save settings to the PMC PMD Change the system time setting Reset accumulated power...

Страница 62: ...ing Time Information The graphic indicator on the right side of the No will reveal the connection status of the module the graphic indicators are as follow Online Offline Connecting 5 13 Modbus Table...

Страница 63: ...module name or information of Module Name will be listed Click on Inquiry to display the Modbus table information of the selected module The users can click on the Print button to print this Modbus ad...

Страница 64: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 49 Figure5 46 Power Meter UID Information Page Users can click Export button to export the UID information as CSV file...

Страница 65: ...options Time Setting Network Setting SNMP Setting Security Setting I O Interface Setting Power Meter Group Setting and Other Setting When you get into the System Setting page the system settings infor...

Страница 66: ...etting Page When get into this page the system will read and display current time of the PMC PMD To modify the system time of PMC PMD set up the date and time on the Time Setting page section and then...

Страница 67: ...Servers to restore the default Time Server settings iii The default Port number setting is 123 currently it is not allowed to be modified iv In the Sync Interval field select the time interval to spec...

Страница 68: ...llows making a change to network configuration web server port or Modbus settings on the PMC PMD The following figure illustrates the configuration interface Please Note PMC 523x PMD series only suppo...

Страница 69: ...ecommunication Service Company To configure the setting for APN and Authentication field please refer to the document provided on the PMC Web page Mobile Code is an optional setting It depends on the...

Страница 70: ...s Service 1 and Service 2 User can enable one Dynamic DNS service for normal status or enable two Dynamic DNS services for the redundant service ii In the Service Provider field select the provider of...

Страница 71: ...IP address the system will logout automatically and re connect to the web page automatically based on the new setting If the connection mode is Obtain an IP address automatically DHCP the system may f...

Страница 72: ...ite Community Name field input a string for Write Community Name for SNMP function The default string is private iv In the Trap Community Name field input a string for Trap Community Name for the SNMP...

Страница 73: ...MP Manager ii Click to Enable or Disable the working model between the SNMP Manager and the SNMP Agent of PMC PMD Currently PMC PMD provides two working models as Read Write Polling and Trap for SNMP...

Страница 74: ...hanges Figure6 12 Save the SNMP Manager Setting 6 4 Security Setting Security Setting allows user to change the password that is required when access to PMC PMD The user could also modify the settings...

Страница 75: ...or Profile Setting section the users could input an email address once the password is forgotten or lost the PMC PMD could send an email with the passwords administrator and guest to this email addres...

Страница 76: ...e time could be set as Disable 10 20 30 60 minutes after the setting is completed click Save button to save the changes Figure6 16 Idle Time Setting Page 6 5 I O Interface Setting I O Interface Settin...

Страница 77: ...set for Modbus TCP Slave to connect HMI or SCADA It can also be set for Modbus TCP Mater to connect Modbus TCP devices PMD 4201 COM1 COM2 RS 485 Reserved for Modbus RTU Master to connect Modbus RTU s...

Страница 78: ...have to be set the same ii In the Parity and Stop bits fields set up the Parity and Stop bits The Parity and Stop bits of PMC PMD and Modbus RTU slave device have to be set the same iii In the Silent...

Страница 79: ...unction on PMC PMD is by default set for Modbus TCP Slave to connect HMI or SCADA User can also select the Modbus TCP Master Checkbox to enable the Modbus TCP Mater function for connecting to Modbus T...

Страница 80: ...o set Carbon Footprint Setting Please input the Carbon Footprint factor based on the Carbon Footprint factors for countries worldwide that the International Energy Agency IEA published 6 7 Power Meter...

Страница 81: ...Figure6 23 Group and Subgroup Viewing 6 7 2 Group and Subgroup Setting i Click the Set up button of group or subgroup to open the setting window Figure6 24 Group Setting Figure6 25 Subgroup Setting ii...

Страница 82: ...done on the Group Subgroup Setting page Please select the group subgroup first and click on the function button to perform the configurations Change Name Click the radio button in front of the group a...

Страница 83: ...the settings of the old group will be copied to this newly added group Remove Click the radio button in front of the group and click on Remove to remove the selected group Close Click the Close butto...

Страница 84: ...x PMC 224x PMD Series User Manual 69 Figure6 29 Choose Loops Phased of Subgroup Figure6 30 Add Loops Phases for Subgroup 6 7 5 Loop Phase of group configuration Figure6 31 Configurations for Loops Pha...

Страница 85: ...lick the radio button in front of the loop phase name and click on Move Up to move the loop phase to upper order upper index number No Move Down Click the radio button in front of the loop phase and c...

Страница 86: ...ia browser after the update is completed the PMC PMD doesn t require to reboot Please follow the steps below i Please contact ICP DAS service to obtain the latest version of the PMC PMD firmware file...

Страница 87: ...through to select the new firmware file and click Open Figure6 33 Firmware Update 2 iv Click Update to update the firmware Figure6 34 Firmware Update 3 v Click OK to start the firmware update to cance...

Страница 88: ...T close the update window or perform any system modification or may result in unexpected failures Figure6 36 Firmware Update 5 vii Click OK to complete the update process After the update is completed...

Страница 89: ...eters and I O Modules that are connected to the PMC PMD After getting into the setting page the overview page will display current setting of the power meters and I O Modules that are connected to the...

Страница 90: ...s RTU and Modbus TCP power meters After all settings are completed click Save button to save the changes Please note 1 PMC PMD provides 2 COM Port RS 485 interface that allows connections to Modbus RT...

Страница 91: ...ters that are connected to the PMC PMD Figure7 3 The Scan button to search Power Meter iii When the Scan page appears Figure 7 4 input the starting address and the ending address of the Modbus address...

Страница 92: ...re 7 7 please select the actual device that are connected to PMC PMD After all settings are completed click Save button to save the changes Figure7 6 The Power Meter List after Scan operation Figure7...

Страница 93: ...odule if the setting is not accurate the connection for PMC PMD to the power meter will be failed Figure7 8 Set up the No and Address of the power meter iii Select the Power meter model Figure7 9 Sele...

Страница 94: ...umber will be the order that the power data of the Modbus TCP power meter being stored in the PMC PMD Modbus Table The range is 1 16 ii Network Set up the settings of IP Port and NetID appropriately a...

Страница 95: ...ter manually 7 1 4 Power Meter List Interface After the Modbus RTU TCP Power Meters are added to the power meter list via auto scan or manual work the Modbus RTU TCP Power Meters will be listed as bel...

Страница 96: ...he pre set power meter and then click on Copy a new power meter in sequence will be added to the list and the settings of the old power meter will be copied to this newly added power meter Remove Clic...

Страница 97: ...the same as the settings of the module if the setting is not accurate the connection for PMC PMD to the power meter will be failed Scan Rate Input the time interval for PMC PMD to periodically retriev...

Страница 98: ...ll be displayed on the Power Meter Information and Rule Setting pages For three phase power meter the user could give nicknames to the Phase A B C After all settings are completed click OK button to r...

Страница 99: ...for each DO channel this nickname will be displayed on the Power Meter Information and Rule Setting pages Power On Value Set up the initial value for the DO channels when the power meter is powered on...

Страница 100: ...module if the setting is not accurate the connection for PMC PMD to the power meter will be failed Scan Rate Input the time interval for PMC PMD to periodically retrieve the power data of this Modbus...

Страница 101: ...ine nicknames for each DO channel this nickname will be displayed on the Power Meter Information and Rule Setting pages Power On Value Set up the initial value for the DO channels when the power meter...

Страница 102: ...ick Setting a window for setting up the parameters of XV Board and its I O channel will appear The setting for the module is shown as below Nickname For user to define a nickname for the module this n...

Страница 103: ...cates that the counter of this DI channel will not function Counter Initial Value Set the initial value of the counter in the Counter Initial Value field This counter will start counting from the init...

Страница 104: ...e dropdown list Pulse Output If the Pulse Output is selected it will allow this DO channel to perform pulse output and form a periodic pulse cycle In Pulse Output mode the selected DO channel will gen...

Страница 105: ...e channels are completed click OK button to return to XV Board Setting page 7 2 3 XV Board AI Channel Settings The XV Board AI Channel Setting page is shown as follow using PMC 5231 XV310 as an exampl...

Страница 106: ...ere are three operation styles for AI Deadband The AI Channel setting in following examples is 0mA 20mA a In the IF Condition when AI or a numerical value Assuming the Deadband value is set to be 2 mA...

Страница 107: ...23 AI Deadband Operation or a numerical value c In the IF Condition when AI a numerical value Assuming the Deadband value is set to be 1 mA and the following statements are defined in the related log...

Страница 108: ...oard AO attribute setting page The settings are as follow Nickname For user to define nicknames for each I O channel this nickname will be displayed on the I O Information and Rule Setting pages Type...

Страница 109: ...he 2 COM Port RS 485 interfaces on PMC PMD allows connections to Modbus RTU I O modules 2 The LAN interface on PMC PMD allows connections to Modbus TCP I O modules For more detailed information of the...

Страница 110: ...dule ii When the Scan page appears Figure 7 28 input the starting address and the ending address of the Modbus address that are going to perform scan Click on Scan the system will start to scan the M...

Страница 111: ...7 30 If the newly scanted module doesn t match the module previously set on the same address a window will appear Figure 7 31 please select the actual device that are connected to PMC PMD After all s...

Страница 112: ...this Modbus RTU module please make sure the address is the same as the settings of the module if the setting is not accurate the connection for PMC PMD to the Modbus RTU module will be failed Figure7...

Страница 113: ...nually add Modbus TCP modules please follow the steps below i No The number will be the order that the I O channel data of the Modbus TCP module being stored in the PMC PMD Modbus Table The range is 1...

Страница 114: ...d click on the function button to perform the operations Setting Click the radio button in front of the Modbus I O module and click on Setting to get into the setting page of the Modbus I O module The...

Страница 115: ...I O Information and Rule Setting pages Description The Description field provides a space for the user to make a brief description of this M 7000 DL module Address The address will be the Modbus addr...

Страница 116: ...r to define nickname for each I O channel this nickname will be displayed on the I O Information and Rule Setting pages Reset counter when power on If the Reset counter when power on is selected for t...

Страница 117: ...The settings are as below Nickname For user to define nickname for each I O channel this nickname will be displayed on the I O Information and Rule Setting pages For M 7000 DL DO channels PMC PMD prov...

Страница 118: ...status is OFF DO0 will set to be OFF as well After all settings are completed click OK button to save the changes and return to Modbus RTU Module List Please Note 1 To set up the Power On value of th...

Страница 119: ...tion and Rule Setting pages Type Select the input signal type of the AI channel from the dropdown list Deadband Please refer to Deadband section in the 7 2 3 XV Board AI Channel Settings for more deta...

Страница 120: ...pe of the AO channel from the dropdown list After all settings are completed click OK button to save the changes and return to Modbus RTU Module List Please note To set up the Power On value of the AO...

Страница 121: ...is nickname will be displayed on the I O Information and Rule Setting pages Description The Description field provides a space for the user to make a brief description of this module Address The addre...

Страница 122: ...te Input Input Register and Holding Register configurations on Modbus RTU Slave module Please Note The number of Modbus address setting blocks will affect the data update rate for the Modbus RTU Slave...

Страница 123: ...address block will be added to the Modbus address mapping table All added address blocks will be located in sequences staring from the Starting Address of the Coil Output The address number on the fir...

Страница 124: ...ame for the address blocks the user can click on the Nickname Setting tab and then input the Nickname for each address block The Nickname will be shown in the I O Information and Rule Setting pages Af...

Страница 125: ...ress and Data Number setting click on Add button A new Discrete Input address block will be added to the Modbus address mapping table All added address blocks will be located in sequences staring from...

Страница 126: ...to assign a Nickname for the address blocks the user can click on the Nickname Setting tab and then input the Nickname for each address block The Nickname will be shown in the I O Information and Rul...

Страница 127: ...er finishing the Start Address setting specify the Data Number it is the number of Input Register data you would like to retrieve from the Start Address Type The system support 6 kinds of data type se...

Страница 128: ...in sequences staring from the Starting Address The address number on the first column of the Local Address indicates the local Modbus address of PMC PMD to keep the Input Register data Figure 7 48 sho...

Страница 129: ...Transformed Value will be saved in floating point format on the PMC PMD no matter what format the raw Input Register value was in the device The default Scale Ratio will be 1 and the default Offset is...

Страница 130: ...Data Model selections to match the Modbus RTU Slave module configuration Please refer to the above section The Coil Output Setting of Modbus RTU Module for detailed information In this case please sel...

Страница 131: ...g Endian will appear Enable Inverse Big Endian to receive the data in big endian format correctly After finishing the Start Address Data Number and Type setting click on Add button A new Holding Regis...

Страница 132: ...e section The Input Register Setting of Modbus RTU Module If the user wants to assign a Nickname for the address blocks the user can click on the Nickname Setting tab and then input the Nickname for e...

Страница 133: ...ormation and Rule Setting pages Description The Description field provides a space for the user to make a brief description of this module IP Allows modification of the IP address of this Modbus TCP S...

Страница 134: ...The time interval to wait for PMC PMD to repeatedly send command again when PMC PMD sends command to the Modbus TCP module and get no response The unit will be second The setting range will be 3 6553...

Страница 135: ...to define his own data recording options from power data I O channel data or Internal Register data The data log files of these two data loggers are both in CSV format that enables easy integration w...

Страница 136: ...ogger I O Data Logger or User Defined Data Logger of the PMC PMD if required The Power Data Logger allows recording the power data of the power meters that are connected to the PMC PMD the I O Data Lo...

Страница 137: ...ame of the power data Please note After enable this function the User Defined Data Logger will also add the Column Header at the beginning of the data logger file to specify the name of the data iv Se...

Страница 138: ...channel for user to check the settings in an easy way The figure above shows an example of the encoded strings the variable C3M3ri4352 indicates the V value of PM 3112 CT1 on the module 3 connected to...

Страница 139: ...ogger 2 The data logger files of Power Data Logger I O Data Logger and User Defined Data Logger all are saved in the micro SD card If the micro SD card s free space is less than the required space of...

Страница 140: ...settings are correct in the Remote FTP Server Setting Test section After clicking Send the system will create a folder on the remote FTP server and will generate a test file under this folder iv In th...

Страница 141: ...I O Data logger files can be upload to remote ICP DAS IoTstar IoT Cloud Management Software The Cloud Upload Setting page is shown as below Figure8 5 Cloud Upload Setting Page Follow the steps below...

Страница 142: ...ily Report Log 01A3851F140000D3_2 3133 7 2013 05 23Rpt csv Monthly Report Log 01A3851F140000D3_2 3133 7 2013 05Rpt csv 01A3851F140000D3_2 3133 7 is the ID of this power meter 01A3851F140000D3 indicate...

Страница 143: ...ord the nickname of the power meter and the related information of the PMC PMD which connect to the power meter The I O Data Log file is also saved under the Log file folder the data file architecture...

Страница 144: ...ltage Current kW kvar kVA PF kWh kvarh kVAh Daily tot Electricity kWh Current demand 15 30 60 mins Reserved Field PM 2134 PM 3112 MTCP PM 3114 MTCP Data Logger Field Date Time Power meter ID CT1 Volta...

Страница 145: ...h kVAh Daily tot Electricity kWh Current demand 15 30 60 mins Reserved Field 8 7 The format of the Power Report file The power report files are saved in CSV format Each line represents one record each...

Страница 146: ...ming of daily max kW daily max kW daily total Electricity Average daily PF Average daily current Average daily voltage Average daily kVA Average daily kvar Reserved Field PM 4324 MTCP PM 4324A MTCP Da...

Страница 147: ...M 4324 MTCP PM 4324A MTCP Monthly Report Date Time Power meter ID Submeter 1 CT1 Timing of daily max kW daily max kW daily total Electricity Average daily PF Average daily current Average daily voltag...

Страница 148: ...iming of daily max kW daily max kW daily total Electricity Average daily PF Average daily current Average daily voltage Average daily kVA Average daily kvar CT24 Timing of daily max kW daily max kW da...

Страница 149: ...data according to the data format and content set by the user In addition the system will tag each data log with information such as date time and type of the data etc The log type could be Period Rec...

Страница 150: ...ive the command message from IoT Cloud Platform to trigger the corresponding actions of PMC PMD at the field side With the IoT Platform Setting function the PMC PMD provides it helps users to implemen...

Страница 151: ...wait for the long TCP IP timeout iv The value in Periodical Publish Interval field defines the time interval to automatically and periodically send the Publish Messages which are with the Periodical...

Страница 152: ...er selects a specific channel it means the specific power data or I O channel value of the module will be bound with the Publish Message If user select All channels it mean all power data and I O chan...

Страница 153: ...he message will be published at periodic time schedule based on the value in Periodical Publish Interval field at Step iv xi After completing all settings of Publish Message please click OK button to...

Страница 154: ...he corresponding value of the Target and Action variables from the message The value of the variables can be used in the evaluation criteria of IF Condition to trigger THEN ELSE Action for logic opera...

Страница 155: ...ow i Check Enable in the Function Status field to enable the connection to IBM Bluemix IoT Cloud Platform ii In the Organization ID Device Type Device ID and Device Authentication Token fields input t...

Страница 156: ...n status to verify the setting is correct or not vi The lower half section on the IBM Bluemix Setting Page is for the Publish Message and Subscribe Message setting User can click the tab of Publish or...

Страница 157: ...ton to save the settings After downloading the settings to the PMC PMD the PMC PMD will initiate the connection to IBM Bluemix and start the Publish Message Subscribe Message mechanism with IBM Bluemi...

Страница 158: ...d the new MQTT Broker After clicking the Add new MQTT Broker the MQTT Broker Setting Page will appear The upper half area of the setting page is about the Broker parameters setting It will be shown as...

Страница 159: ...encryption mechanism is required for the connection between the Broker and the PMC PMD via MQTT click the Enable checkbox of the Encryption field to enable this function x The value in keep alive Tim...

Страница 160: ...be the model name of the PMC PMD If there are more than one PMC PMD controllers in a system for MQTT connection please remember to change the Topic Prefix setting to distinguish the Publish Topic Subs...

Страница 161: ...alue of the module will be bound with the Publish Message If user select All channels it mean all power data and I O channel values of the module will be added in the Publish Message List If the user...

Страница 162: ...the variation exceeds xxx and Periodical Publish If the When the I O channel data changed and the variation exceeds xxx is selected the system will automatically publish the topic when the power data...

Страница 163: ...c It allows user to change the value of the Internal Register and the value of the output channel of I O module or power meter by MQTT protocol Please refer to Appendix VI for detailed information xxv...

Страница 164: ...T Topic To use the Topic Import function please prepare a document with the same format as The_nickname_of_Topic Topic message Click the Import Topic button then browse through to select the document...

Страница 165: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 150 Figure9 14 The Import of MQTT Topic...

Страница 166: ...note In order to avoid possible error when performing rule definition IF THEN ELSE please always finish configuration in Advanced Setting before starting to define Rules Avoid unnecessary change in Ad...

Страница 167: ...ield shown as below Figure10 2 Email setting page Name Description iii In the SMTP Server field enter the IP or the domain name of the SMTP server or select the SMTP server from the dropdown list In t...

Страница 168: ...sword field viii In the Security field select the security setting to be No Security TLS or SSL from the dropdown list ix After complete SMTP server setting continue to input Email address setting In...

Страница 169: ...detailed information of the Real time variable editor xiv Click on OK to confirm the setting and leave the setting page xv Repeat steps i xv to complete settings of all Emails To modify the settings o...

Страница 170: ...d phone numbers only There are 2 types of SMS commands Retrieve channel data GET The user can retrieve specific channel real time data One SMS Command message can require up to 10 channel data values...

Страница 171: ...ter the content in the Message field If the Unicode mode is adopted the length of the content cannot exceed 70 characters If the Unicode mode is not selected will support English characters only the l...

Страница 172: ...ove a pre set SMS Alarm please click the radio button in front of the pre set SMS Alarm and then click Remove xii After you finish all the SMS Alarm selections and settings click Save button to save t...

Страница 173: ...ommand in the Command String Editor section In the Command String Editor section select the command type to be GET retrieve real time channel data or SET modify channel data from the dropdown list For...

Страница 174: ...and Setting for SET Command vii Click on OK to confirm the setting and leave the setting page viii Repeat steps v vii to complete settings of all SMS Command setting The SMS Command and its original c...

Страница 175: ...when user send SMS message DO to PMC 5231 3GWA PMC 5231 3GWA will set the value of DO0 on XV Board to be ON after receiving the message ix To modify the settings of a pre set SMS Command please click...

Страница 176: ...NMP Trap setting is shown as below Figure10 12 SNMP Trap Setting Page The settings steps are as below i Input Nickname and Specific ID and then click button to create a new SNMP Trap ii To modify the...

Страница 177: ...nnel Data type The setting page interface will be shown as below Figure10 14 Channel Data Type Setting Page Based on the Channel Data type interface it provides the encoded string for user to easily a...

Страница 178: ...low Figure10 16 User Defined Data Type Setting Page Set up the content in the User Defined Data field of the SNMP Trap Variable Binding Setting Page The User Defined Data provides encoded strings for...

Страница 179: ...n editing the content the user can select the View tab and then the channel encoded string will be displayed in the real index format of the channel for user to check the settings in an easy way The f...

Страница 180: ...bindings setting and return to the SNMP Trap Setting Page Figure10 19 SNMP Trap setting with variable bindings list viii To copy the settings of a pre set SNMP Trap to the new SNMP Trap please click t...

Страница 181: ...ge users have to apply a LINE Notify service first and connect the service with the personal account or chat room to be sent Please refer to the LINE Notify guide webpage on PMMS official webpage for...

Страница 182: ...d iv Enter the message content in the Content field LINE message provides an encoded string for you to add current power data I O channel data or Internal Register data into LINE messages To make it e...

Страница 183: ...oom please refer to the section 10 4 2 Chat Room Setting Figure10 23 LINE Notify Message Setting page 4 vi After complete all settings click the OK button to confirm the LINE Notify message setting an...

Страница 184: ...ar as below Input the Client ID and Client Secret of the applied service and click the Send button the LINE login interface will appear if the client data was correct If you do not apply the service b...

Страница 185: ...t this account one to one or a group under this account which PMC PMD will connect to Figure10 27 LINE Notify Chat Room Setting page 4 iv After the connection procedure is complete the new chat room w...

Страница 186: ...LINE accounts to join the group to receive the messages from PMC PMD 10 5 Messenger Setting PMC PMD provides Facebook Messenger message sending function With this function PMC PMD can send message to...

Страница 187: ...ook Fan Page In order to enable the PMC Messenger message sending function user must have the administration authority of the specified Facebook Fan Page first then PMC PMD would send the messages to...

Страница 188: ...s User Manual 173 9 55 Facebook Figure10 29 Create a Fan Page Select the appropriate category for the Fan page You can select the Product Service category in the Brand or Product section Figure10 30 C...

Страница 189: ...Facebook Fan Page will be shown as below Figure10 31 The creation of the Facebook Fan Page is Done After the Facebook Fan Page is created it will be automatically opened The administrator can set the...

Страница 190: ...k then user can directly scan the QR code to go to the Facebook Fan page Figure10 33 Publish the QR Code of the Fan Page If the Facebook users want to receive the message sent by PMC PMD they must act...

Страница 191: ...bpage Computer Following is the steps required to create the connection between the user of Facebook and the Facebook Fan Page By using Facebook APP Mobile phone Following is the steps required to cre...

Страница 192: ...cess Token of the Facebook Fan Page Here are the steps to create an App and get the token i Go to the facebook for developers page and log in the page by using your personal account of Facebook https...

Страница 193: ...nput the name of the App In this example the App is named as PMC Controller System After complete the setting click the Create App ID button to create the App Figure10 36 Create a New App iv After the...

Страница 194: ...send the messages to all the Fackbook accounts who are complete the interaction with the Facebook Fan Page 10 5 3 Edit message receiving list After the App is created only the administrators developer...

Страница 195: ...ok user to search for the user and send an invitation If the Facebook user is not the friend of the administrator s Facebook account the administrator must enter the username or fbid of the Facebook u...

Страница 196: ...ook Fan Page now user can use the Token to set up the parameters of Messenger message sending function which PMC PMD require and PMC PMD will send the messages to all Fackbook accounts who are complet...

Страница 197: ...Fan Page to enable the connection between PMC PMD and Facebook Fan Page User can click the Testing in the Connection Testing field to verify whether the message can be sent correctly or not ii Click...

Страница 198: ...the Facebook Fan Page at least once The Messenger only supports UTF 8 format for the Text messages and the message can not exceed 2000 characters 10 6 Timer Setting PMC PMD provides Timer for timing f...

Страница 199: ...internal register as timer period Please refer to ch 10 8 Internal Register Setting to setup internal register iv Click button to create a new Timer Figure10 46 Timer creating Page v Repeat steps i i...

Страница 200: ...ase click the radio button in front of the pre set Timer and then click Remove ix After all timer settings are completed click Save button to save the changes 10 7 Schedule Setting PMC PMD provides Sc...

Страница 201: ...n the Date section the calendars corresponding to the Year and Month you specified will appear as shown below Figure10 50 Calendar mode of Schedule setting b In the Time Range s section click Add to a...

Страница 202: ...be In Range that is during the date range you select the operation will be executed every day Select All button is used to set all dates to be In Range whereas Unselect All button is for marking all d...

Страница 203: ...set one day after the start date Click Remove to remove a pre set Time Range iv Click on OK to confirm the setting and leave the setting page v Repeat steps i iv to complete settings of all Schedule v...

Страница 204: ...cription field iii Setup the calculation expressions of the Total Facility Energy and users can click add button to modify the expressions iv Setup the calculation expressions of the IT Equipment Ener...

Страница 205: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 190 Figure10 53 PUE Setting Page 2...

Страница 206: ...will be retained even the PMC PMD is in Power Off status The configuration page is shown as follow Figure10 54 Internal Register setting page 1 The settings steps are as below i Select the number of...

Страница 207: ...ernal register and then click Copy a new internal register in sequence will be added to the list and the settings of the old internal register will be copied to this newly added internal register iv T...

Страница 208: ...face will also be shown on the left side of the page Detailed description is as below Add new rule To add a new rule please click Add new rule Copy To copy the settings of an old rule to the new rule...

Страница 209: ...THEN ELSE Action setting click on Save to save the settings Please note if you make modification in Power meter setting IO module setting or in Advanced Setting after finish defining the rules it migh...

Страница 210: ...ent to arrange the components into appropriate order The following section will give more detailed information of IF Condition and THEN ELSE Action settings 11 1 IF Condition Setting To add an IF Cond...

Страница 211: ...d M 7000 DL 3 options will appear as the following DI DI Counter and AI 11 1 1 1 DI DI channel value from XV Board M 7000 module can be used as evaluation criteria for IF condition statement the setti...

Страница 212: ...from the dropdown list to be User Defined or Internal Register If User Defined is selected input the User Defined value under the Value section If Internal Register is selected select the number of t...

Страница 213: ...result of this condition evaluation will be true iv PMC PMD provides the following 7 values options you can compare them with the AI channel value for condition evaluation User Defined The User Defin...

Страница 214: ...nnel from the dropdown list to specify which channel value will be used Holding Register The Holding Register value from other Modbus RTU TCP Slave modules could be used as evaluation criteria select...

Страница 215: ...Discrete Input channel value from Modbus TCP RTU Slave module can be included in the IF condition statements the editing page for Discrete Input Condition Setting is shown as below Figure11 6 Discrete...

Страница 216: ...i Click OK button to confirm the settings and return to the Rule settings page 11 1 2 3 Input Register Input Register channel value from Modbus TCP RTU Slave module can be included in the IF condition...

Страница 217: ...hown as below Figure11 9 Holding Register condition setting page Follow the steps below i Specify the module and address of the Modbus TCP RTU Slave module from the dropdown list of the Module Address...

Страница 218: ...the Module Address section that you are going to include its value in the IF condition statements ii Set up the expression statement for this power data value of the Power Meter Select an operator fro...

Страница 219: ...ibe Message from Microsoft Azure can be used in the IF condition statements the editing page for Microsoft Azure Subscribe Message condition setting is shown as below Figure11 12 Microsoft Azure Subsc...

Страница 220: ...s shown as below Figure11 13 IBM Bluemix Connection Status condition setting Follow the steps below i Specify the connection status to be Offline or Online If the connection status of IBM Bluemix matc...

Страница 221: ...ues options you can compare them with the content of this Subscribe Topic for condition evaluation Please refer to 11 1 1 3 AI for detail iv Click OK button to confirm the settings and return to the R...

Страница 222: ...nd Topic field that you are going to include them in the IF condition statements ii Set up the expression statement for the content of this Subscribe Topic Select an operator from or iiiSpecify the us...

Страница 223: ...the Rule settings page 11 1 8 Timer Timer condition can be used as evaluation criteria for IF condition statement the editing page for timer condition setting is shown as follow Figure11 18 Timer cond...

Страница 224: ...ue iii Click OK button to confirm the settings and return to the Rule settings page 11 1 10 Mobile Network Signal Strength The Mobile Network Signal Strength can be used as evaluation criteria for IF...

Страница 225: ...ad files via FTP once the time period reaches the maximum allowable idle time period the result of this condition evaluation will be true ii Click OK button to confirm the settings and return to the R...

Страница 226: ...ropdown list of the Rule field ii Specify the Rule status to be Disable or Enable from the dropdown list of the Status field When the Rule status matches the specified status the evaluation result wil...

Страница 227: ...l Register value match the evaluation criteria the result of this condition evaluation will be true iv PMC PMD provides 7 value options you can compare them with the Input Register value for condition...

Страница 228: ...ist To include subjects other than modules mentioned above in the THEN ELSE Action statement they have to be pre defined in Advanced Setting first The setting options of the subjects that already bein...

Страница 229: ...Counter DO and AO 11 2 1 1 DI Counter You can reset DI counter of the XV Board M 7000 modules in the THEN ELSE Action statement the editing page for DI counter Action is shown as follow Figure11 25 DI...

Страница 230: ...the value in the Waiting Time field it means after the action be executed how long the system will delay to execute the next Action The unit will be second s v Click OK button to confirm the settings...

Страница 231: ...fined Input a User Defined value under the Value field Internal Register Select the number of the Internal Register from the dropdown list AI Using AI channel values from XV Board M 7000 DL select the...

Страница 232: ...Total Electricity and Yearly Total Electricity etc And then select the power meter and loop or phase from the dropdown list to specify which power meter and loop or phase value will be used iv Specif...

Страница 233: ...n list of the Status field The output value can be OFF or ON iii Specify the Frequency to be One Time or Repeat iv Specify the value in the Waiting Time field it means after the action be executed how...

Страница 234: ...up the value in the Value field PMC PMD provides 7 value options Please refer to 11 2 1 3 AO section for more detailed information for value settings of these 7 options iv Specify the Frequency to be...

Страница 235: ...gs page 11 2 4 Microsoft Azure Click on Microsoft Azure 3 options will appear as the following Function Status Publish Message and Reset Variable 11 2 4 1 Function Status User can execute an action to...

Страница 236: ...ble You can reset the saved content of the subscribe variable from Microsoft Azure when executing a THEN ELSE Action statement the editing page is shown as below Figure11 33 Microsoft Azure Reset Vari...

Страница 237: ...eration between IBM Bluemix and PMC PMD to be Disable or Enable from the dropdown list of the Status field ii Click OK button to confirm the settings and return to the Rule settings page 11 2 5 2 Publ...

Страница 238: ...ield When this action is executed PMC PMD would reset the content of the variable and the evaluation result of the IF statement which is associated with the variable will be verified again ii Click OK...

Страница 239: ...an publish a MQTT Topic to the Broker when executing a THEN ELSE Action statement the editing page is shown as below Figure11 38 Publish Message action setting page Follow the steps below i Select a p...

Страница 240: ...imer You can change the Timer status to Start or to Reset the Timer in the THEN ELSE Action statement the editing page for Timer Action Setting is shown as below Figure11 40 Timer action setting page...

Страница 241: ...steps below i Select a pre set Email group from the dropdown list of the Index field Please note the Email you select has to be enabled in Advanced Setting The Email group information will be display...

Страница 242: ...Figure11 43 SNMP Trap Action Setting Page Follow the steps below i In the Trap field specify the SNMP Trap you want to execute in Action from the dropdown list Please note the SNMP Trap you select has...

Страница 243: ...the steps below i In the Message field specify the LINE message you want to send in Action from the dropdown list The selected LINE Notify message such as Chat Room and message content will be display...

Страница 244: ...red User can also perform Start or Stop operation on data logger The setting page is show as below Figure11 46 Data Logger action setting page Follow the steps below i In the Action field specify the...

Страница 245: ...ct the pre defined Internal Register from the dropdown list of the No field Please note the Internal Register you select has to be enabled in Advanced Setting ii Specify the Operator in the Operator f...

Страница 246: ...e Value field PMC PMD provides 7 value options Please refer to 11 2 1 3 AO section for more detailed information for value settings of these 7 options iv Specify the Frequency to be One Time or Repeat...

Страница 247: ...ing code example demonstrates how to join the two registers into one floating point value For the compilers are different big endian or little endian the floating point composing order might be differ...

Страница 248: ...D 4201 COM1 COM2 Modbus Address Coil Output 0x Discrete Input 1x Input Register 3x Holding Register 4x 0 59 PMC PMD System Data 1 60 75 RS 485 1 connection status 2 RS 485 1 Information 3 Internal Reg...

Страница 249: ...9 Power Meter Information Index 1 of RS 485 1 7 20250 20299 Power Meter Information Index 2 of RS 485 1 7 20300 20349 Power Meter Information Index 3 of RS 485 1 7 20350 20399 Power Meter Information...

Страница 250: ...40200 40249 Power Meter Information Index 1 of RS 485 2 7 40250 40299 Power Meter Information Index 2 of RS 485 2 7 40300 40349 Power Meter Information Index 3 of RS 485 2 7 40350 40399 Power Meter In...

Страница 251: ...6 of LAN 7 60200 60249 Power Meter Information Index 1 of LAN 7 60250 60299 Power Meter Information Index 2 of LAN 7 60300 60349 Power Meter Information Index 3 of LAN 7 60350 60399 Power Meter Inform...

Страница 252: ...0 1 UInt16 0 65535 Serial Number 8 300011 1 UInt16 0 65535 Boot Date Year 300012 1 UInt16 1752 Boot Date Month 300013 1 UInt16 1 12 Boot Date Day 300014 1 UInt16 1 31 Boot Time Hour 300015 1 UInt16 0...

Страница 253: ...s of M 7000 DL IR power meter and Modbus TCP RTU modules that are connected to the PMC PMD detailed information is shown as below Parameter Name Modbus Address Length Data Type Range 1x Discrete Input...

Страница 254: ...e connected to RS 485 2 300076 300091 1 UInt16 7002 7088 2133 4324 Module Address 1 64 The module type or NetID of power meter or Modbus TCP modules that are connected to LAN 300092 300107 1 UInt16 21...

Страница 255: ...ress the following section shows corresponding address information for different modules XV107 XV107A Parameter Name Modbus Address Length Data Type Range Coil Output 0x Unit Coil 8 Bits DO Ch 0 00020...

Страница 256: ...F 1 ON DI Ch 3 100203 1 Byte 0 OFF 1 ON DI Ch 4 100204 1 Byte 0 OFF 1 ON DI Ch 5 100205 1 Byte 0 OFF 1 ON DI Ch 6 100206 1 Byte 0 OFF 1 ON DI Ch 7 100207 1 Byte 0 OFF 1 ON DI Ch 8 100208 1 Byte 0 OFF...

Страница 257: ...t 0x Unit Coil 8 Bits DO Ch 0 000200 1 Byte 0 OFF 1 ON DO Ch 1 000201 1 Byte 0 OFF 1 ON DO Ch 2 000202 1 Byte 0 OFF 1 ON DO Ch 3 000203 1 Byte 0 OFF 1 ON DO Ch 4 000204 1 Byte 0 OFF 1 ON DO Ch 5 00020...

Страница 258: ...DI Counter 3 300206 2 UInt32 0 4294967295 DI Counter 4 300208 2 UInt32 0 4294967295 XV306 Parameter Name Modbus Address Length Data Type Range Coil Output 0x Unit Coil 8 Bits DO Ch 0 000200 1 Byte 0...

Страница 259: ...0203 1 Byte 0 OFF 1 ON Input Register 3x Unit Register 16 Bits DI Counter 0 300200 2 UInt32 0 4294967295 DI Counter 1 300202 2 UInt32 0 4294967295 DI Counter 2 300204 2 UInt32 0 4294967295 DI Counter...

Страница 260: ...Float Floating Point AI Ch 5 300210 2 Float Floating Point AI Ch 6 300212 2 Float Floating Point AI Ch 7 300214 2 Float Floating Point DI Counter 0 300216 2 UInt32 0 4294967295 DI Counter 1 300218 2 U...

Страница 261: ...ounter 3 300214 2 UInt32 0 4294967295 Holding Register 4x Unit Register 16 Bits AO Ch 0 400200 2 Float Floating Point AO Ch 1 400202 2 Float Floating Point 6 PUE Data This block stores information of...

Страница 262: ...e connection port and the index number PM_SA The starting Modbus address of Power Meter Information 2 of the connection port Power Meter Index number 1 x 50 4 Check the Modbus Address Table of each ty...

Страница 263: ...Byte 0 OFF 1 ON 3x Input Register Unit Register 16 Bits AI Ch 0 SA 300000 2 Float Floating Point AI Ch 1 SA 300002 2 Float Floating Point AI Ch 2 SA 300004 2 Float Floating Point AI Ch 3 SA 300006 2 F...

Страница 264: ...gth Data Type Range 0x Coils Output Unit Coil 8 Bits DO Ch 0 SA 000000 1 Byte 0 OFF 1 ON DO Ch 1 SA 000001 1 Byte 0 OFF 1 ON 1x Discrete Input Unit Coil 8 Bits DI Ch 0 SA 100000 1 Byte 0 OFF 1 ON 3x I...

Страница 265: ...nt AI Ch 1 SA 300002 2 Float Floating Point DI Counter 0 SA 300004 1 UInt16 0 65535 4x Holding Register Unit Register 16 Bits AO Ch 0 SA 400000 2 Float Floating Point M 7017 M 7017R M 7017C M 7017RC M...

Страница 266: ...M 7017Z 20 Single Ended AI channel Parameter Name Modbus Address Length Data Type Range 3x Input Register Unit Register 16 Bits AI Ch 0 SA 300000 2 Float Floating Point AI Ch 1 SA 300002 2 Float Floa...

Страница 267: ...SA 300008 2 Float Floating Point AI Ch 5 SA 300010 2 Float Floating Point AI Ch 6 SA 300012 2 Float Floating Point AI Ch 7 SA 300014 2 Float Floating Point AI Ch 8 SA 300016 2 Float Floating Point AI...

Страница 268: ...Register Unit Register 16 Bits AO Ch 0 SA 400000 2 Float Floating Point AO Ch 1 SA 400002 2 Float Floating Point AO Ch 2 SA 400004 2 Float Floating Point AO Ch 3 SA 400006 2 Float Floating Point M 700...

Страница 269: ...OFF 1 ON DI Ch 8 SA 100008 1 Byte 0 OFF 1 ON DI Ch 9 SA 100009 1 Byte 0 OFF 1 ON DI Ch 10 SA 100010 1 Byte 0 OFF 1 ON DI Ch 11 SA 100011 1 Byte 0 OFF 1 ON DI Ch 12 SA 100012 1 Byte 0 OFF 1 ON DI Ch 13...

Страница 270: ...SA 300002 2 UInt32 0 4294967295 M 7084 8 Counter Frequency Parameter Name Modbus Address Length Data Type Range 3x Input Register Unit Register 16 Bits DI Counter 0 SA 300000 2 UInt32 0 4294967295 DI...

Страница 271: ...5 1 Byte 0 OFF 1 ON DI Ch 6 SA 100006 1 Byte 0 OFF 1 ON DI Ch 7 SA 100007 1 Byte 0 OFF 1 ON 3x Input Register Unit Register 16 Bits DI Counter 0 SA 300000 2 UInt32 0 4294967295 DI Counter 1 SA 300002...

Страница 272: ...Point Temperature F SA 300006 2 Float Floating Point Dew Point C SA 300008 2 Float Floating Point Dew Point F SA 300010 2 Float Floating Point IR 210 Parameter Name Modbus Address Length Data Type Ran...

Страница 273: ...2 Float Floating Point kvar SA 300024 2 Float Floating Point kVA SA 300026 2 Float Floating Point PF SA 300028 2 Float Floating Point kWh SA 300030 2 Float Floating Point kvarh SA 300032 2 Float Floa...

Страница 274: ...Monthly SA 300080 2 Float Floating Point Daily Accumulated Electricity SA 300082 2 Float Floating Point Monthly Accumulated Electricity SA 300084 2 Float Floating Point Yearly Accumulated Electricity...

Страница 275: ...y Accumulated Electricity SA 300114 2 Float Floating Point Monthly Accumulated Electricity SA 300116 2 Float Floating Point Yearly Accumulated Electricity SA 300118 2 Float Floating Point Total Averag...

Страница 276: ...Float 1 65535 PM 2134 Parameter Name Modbus Address Length Data Type Range 3x Input Register Unit Register 16 Bits CT1 V SA 300000 2 Float Floating Point I SA 300002 2 Float Floating Point kW SA 3000...

Страница 277: ...Floating Point kW SA 300058 2 Float Floating Point kvar SA 300060 2 Float Floating Point kVA SA 300062 2 Float Floating Point PF SA 300064 2 Float Floating Point kWh SA 300066 2 Float Floating Point k...

Страница 278: ...Float Floating Point Monthly Accumulated Electricity SA 300100 2 Float Floating Point Yearly Accumulated Electricity SA 300102 2 Float Floating Point CT3 15 30 60 mins Actual Demand SA 300104 2 Float...

Страница 279: ...ectricity SA 300130 2 Float Floating Point Monthly Accumulated Electricity SA 300132 2 Float Floating Point Yearly Accumulated Electricity SA 300134 2 Float Floating Point 3x Input Register Unit Regis...

Страница 280: ...oating Point kvar SA 300006 2 Float Floating Point kVA SA 300008 2 Float Floating Point PF SA 300010 2 Float Floating Point kWh SA 300012 2 Float Floating Point kvarh SA 300014 2 Float Floating Point...

Страница 281: ...Point kVAh SA 300070 2 Float Floating Point Phase A 15 30 60 mins Actual Demand SA 300072 2 Float Floating Point 15 30 60 mins Forecast Demand SA 300074 2 Float Floating Point Max Demand Hourly SA 300...

Страница 282: ...s Forecast Demand SA 300106 2 Float Floating Point Max Demand Hourly SA 300108 2 Float Floating Point Max Demand Daily SA 300110 2 Float Floating Point Max Demand Monthly SA 300112 2 Float Floating Po...

Страница 283: ...loat Floating Point Frequency Phase C SA 300144 2 Float Floating Point Frequency Maximum SA 300146 2 Float Floating Point 3x Input Register Unit Register 16 Bits Power Meter Type PM_SA 300000 1 Int16...

Страница 284: ...kvarh SA 300014 2 Float Floating Point kVAh SA 300016 2 Float Floating Point CT2 V SA 300018 2 Float Floating Point I SA 300020 2 Float Floating Point kW SA 300022 2 Float Floating Point kvar SA 3000...

Страница 285: ...SA 300048 2 Float Floating Point Yearly Accumulated Electricity SA 300050 2 Float Floating Point CT2 15 30 60 mins Actual Demand SA 300052 2 Float Floating Point 15 30 60 mins Forecast Demand SA 3000...

Страница 286: ...ister Unit Register 16 Bits CT1 V SA 300000 2 Float Floating Point I SA 300002 2 Float Floating Point kW SA 300004 2 Float Floating Point kvar SA 300006 2 Float Floating Point kVA SA 300008 2 Float Fl...

Страница 287: ...2 Float Floating Point PF SA 300064 2 Float Floating Point kWh SA 300066 2 Float Floating Point kvarh SA 300068 2 Float Floating Point kVAh SA 300070 2 Float Floating Point CT1 15 30 60 mins Actual De...

Страница 288: ...city SA 300102 2 Float Floating Point CT3 15 30 60 mins Actual Demand SA 300104 2 Float Floating Point 15 30 60 mins Forecast Demand SA 300106 2 Float Floating Point Max Demand Hourly SA 300108 2 Floa...

Страница 289: ...CT2 SA 300138 2 Float Floating Point Frequency CT3 SA 300140 2 Float Floating Point Frequency CT4 SA 300142 2 Float Floating Point 3x Input Register Unit Register 16 Bits Power Meter Type PM_SA 300000...

Страница 290: ...e 1 Phase A CT1 2 Phase B CT2 3 Phase C CT3 Harmonic Selector Submeter 2 SA 400001 1 UInt16 0 Disable 1 Phase A CT4 2 Phase B CT5 3 Phase C CT6 Harmonic Selector Submeter 3 SA 400002 1 UInt16 0 Disabl...

Страница 291: ...Point kvarh SA 300014 2 Float Floating Point kVAh SA 300016 2 Float Floating Point Phase B CT2 V SA 300018 2 Float Floating Point I SA 300020 2 Float Floating Point kW SA 300022 2 Float Floating Poin...

Страница 292: ...oat Floating Point kWh SA 300084 2 Float Floating Point kvarh SA 300086 2 Float Floating Point kVAh SA 300088 2 Float Floating Point Phase B CT5 V SA 300090 2 Float Floating Point I SA 300092 2 Float...

Страница 293: ...oat Floating Point kWh SA 300156 2 Float Floating Point kvarh SA 300158 2 Float Floating Point kVAh SA 300160 2 Float Floating Point Phase B CT8 V SA 300162 2 Float Floating Point I SA 300164 2 Float...

Страница 294: ...oat Floating Point kWh SA 300228 2 Float Floating Point kvarh SA 300230 2 Float Floating Point kVAh SA 300232 2 Float Floating Point Phase B CT11 V SA 300234 2 Float Floating Point I SA 300236 2 Float...

Страница 295: ...oat Floating Point kWh SA 300300 2 Float Floating Point kvarh SA 300302 2 Float Floating Point kVAh SA 300304 2 Float Floating Point Phase B CT14 V SA 300306 2 Float Floating Point I SA 300308 2 Float...

Страница 296: ...oat Floating Point kWh SA 300372 2 Float Floating Point kvarh SA 300374 2 Float Floating Point kVAh SA 300376 2 Float Floating Point Phase B CT17 V SA 300378 2 Float Floating Point I SA 300380 2 Float...

Страница 297: ...oat Floating Point kWh SA 300444 2 Float Floating Point kvarh SA 300446 2 Float Floating Point kVAh SA 300448 2 Float Floating Point Phase B CT20 V SA 300450 2 Float Floating Point I SA 300452 2 Float...

Страница 298: ...oat Floating Point kWh SA 300516 2 Float Floating Point kvarh SA 300518 2 Float Floating Point kVAh SA 300520 2 Float Floating Point Phase B CT23 V SA 300522 2 Float Floating Point I SA 300524 2 Float...

Страница 299: ...30 60 mins Forecast Demand SA 300578 2 Float Floating Point Max Demand Hourly SA 300580 2 Float Floating Point Max Demand Daily SA 300582 2 Float Floating Point Max Demand Monthly SA 300584 2 Float Fl...

Страница 300: ...A 300612 2 Float Floating Point Max Demand Daily SA 300614 2 Float Floating Point Max Demand Monthly SA 300616 2 Float Floating Point Daily Accumulated Electricity SA 300618 2 Float Floating Point Mon...

Страница 301: ...urly SA 300644 2 Float Floating Point Max Demand Daily SA 300646 2 Float Floating Point Max Demand Monthly SA 300648 2 Float Floating Point Daily Accumulated Electricity SA 300650 2 Float Floating Poi...

Страница 302: ...0676 2 Float Floating Point Max Demand Daily SA 300678 2 Float Floating Point Max Demand Monthly SA 300680 2 Float Floating Point Daily Accumulated Electricity SA 300682 2 Float Floating Point Monthly...

Страница 303: ...SA 300708 2 Float Floating Point Max Demand Daily SA 300710 2 Float Floating Point Max Demand Monthly SA 300712 2 Float Floating Point Daily Accumulated Electricity SA 300714 2 Float Floating Point M...

Страница 304: ...A 300740 2 Float Floating Point Max Demand Daily SA 300742 2 Float Floating Point Max Demand Monthly SA 300744 2 Float Floating Point Daily Accumulated Electricity SA 300746 2 Float Floating Point Mon...

Страница 305: ...urly SA 300772 2 Float Floating Point Max Demand Daily SA 300774 2 Float Floating Point Max Demand Monthly SA 300776 2 Float Floating Point Daily Accumulated Electricity SA 300778 2 Float Floating Poi...

Страница 306: ...A 300804 2 Float Floating Point Max Demand Daily SA 300806 2 Float Floating Point Max Demand Monthly SA 300808 2 Float Floating Point Daily Accumulated Electricity SA 300810 2 Float Floating Point Mon...

Страница 307: ...urly SA 300836 2 Float Floating Point Max Demand Daily SA 300838 2 Float Floating Point Max Demand Monthly SA 300840 2 Float Floating Point Daily Accumulated Electricity SA 300842 2 Float Floating Poi...

Страница 308: ...A 300868 2 Float Floating Point Max Demand Daily SA 300870 2 Float Floating Point Max Demand Monthly SA 300872 2 Float Floating Point Daily Accumulated Electricity SA 300874 2 Float Floating Point Mon...

Страница 309: ...urly SA 300900 2 Float Floating Point Max Demand Daily SA 300902 2 Float Floating Point Max Demand Monthly SA 300904 2 Float Floating Point Daily Accumulated Electricity SA 300906 2 Float Floating Poi...

Страница 310: ...A 300932 2 Float Floating Point Max Demand Daily SA 300934 2 Float Floating Point Max Demand Monthly SA 300936 2 Float Floating Point Daily Accumulated Electricity SA 300938 2 Float Floating Point Mon...

Страница 311: ...urly SA 300964 2 Float Floating Point Max Demand Daily SA 300966 2 Float Floating Point Max Demand Monthly SA 300968 2 Float Floating Point Daily Accumulated Electricity SA 300970 2 Float Floating Poi...

Страница 312: ...A 300996 2 Float Floating Point Max Demand Daily SA 300998 2 Float Floating Point Max Demand Monthly SA 301000 2 Float Floating Point Daily Accumulated Electricity SA 301002 2 Float Floating Point Mon...

Страница 313: ...urly SA 301028 2 Float Floating Point Max Demand Daily SA 301030 2 Float Floating Point Max Demand Monthly SA 301032 2 Float Floating Point Daily Accumulated Electricity SA 301034 2 Float Floating Poi...

Страница 314: ...A 301060 2 Float Floating Point Max Demand Daily SA 301062 2 Float Floating Point Max Demand Monthly SA 301064 2 Float Floating Point Daily Accumulated Electricity SA 301066 2 Float Floating Point Mon...

Страница 315: ...int Submeter 2 VTHD SA 301092 2 Float Floating Point Submeter 2 ITHD SA 301094 2 Float Floating Point Submeter 3 VTHD SA 301096 2 Float Floating Point Submeter 3 ITHD SA 301098 2 Float Floating Point...

Страница 316: ...Floating Point Frequency CT6 Phase C SA 301132 2 Float Floating Point Frequency Maximum SA 301134 2 Float Floating Point Frequency CT7 Phase A SA 301136 2 Float Floating Point Frequency CT8 Phase B SA...

Страница 317: ...nt Frequency Maximum SA 301174 2 Float Floating Point Frequency CT22 Phase A SA 301176 2 Float Floating Point Frequency CT23 Phase B SA 301178 2 Float Floating Point Frequency CT24 Phase C SA 301180 2...

Страница 318: ...Ratio 2 PM_SA 300014 2 Float 0 01 655 35 CT Ratio 1 PM_SA 300016 2 Float 1 65535 CT Ratio 2 PM_SA 300018 2 Float 1 65535 CT Ratio 3 PM_SA 300020 2 Float 1 65535 CT Ratio 4 PM_SA 300022 2 Float 1 6553...

Страница 319: ...Data Number Coil Output 11 7 Discrete Input 0 10 Input Register 7 4 32 bit Floating Point Holding Register 20 3 32 bit Floating Point The allocation of the Modbus Address in PMC PMD for the Coil Outpu...

Страница 320: ...13407 9 10008 13408 10 10009 13409 The allocation of the Modbus Address in PMC PMD for the Input Register setting of this Modbus RTU module is shown as below Input Register Index The Modbus Address in...

Страница 321: ...itch to the specific position to delete the data logger files and reset the accumulated values of the power meter which connect to PMC PMD The following figure shows the location of the Rotary Switch...

Страница 322: ...witch to position 8 2 Connect to PMC PMD Login webpage via Web browser Now a Forget password message will be displayed under the password field Click the Forget password message then the system will s...

Страница 323: ...otary Switch to position 8 2 Connect to PMC PMD login webpage via Web browser and login as the Administrator 3 After login into the system the message box of Delete the data logger files and reset the...

Страница 324: ...the GTM 203M 3GWA with PMD Hardware installation 1 Install the SIM card and antenna on the GTM 203M 3GWA and connect the device with Power 10VDC 30VDC 2 Connect the GTM 203M 3GWA and PMD by USB cable...

Страница 325: ...ct the M 7000 DL modules to the PC with DCON Utility installed via RS 485 cable make sure the RS 485 cable is properly connected For PC to receive RS 485 signals a RS 232 to RS 485 or a USB to RS 485...

Страница 326: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 311 B Start the DCON Utility and verify if the COM Port parameters are accurate...

Страница 327: ...ted to the PC C Click on the M 7000 module to bring up the Configuration Window and setup the parameters such as Address Baudrate for the module The Configuration Window will be shown as follow using...

Страница 328: ...as below http ftp icpdas com pub cd 8000cd napdos driver dcon_utility manual 3 For others ICP DAS I O module please refer to related user manual for the configuration setting In order to accurately co...

Страница 329: ...Index ifDescr IfType ifMtu ifSpeed ifPhysAddress ifAdminStatus ifOperStatus ifLastChange ifInOctets ifInUcastPkts ifInNUcastPkts ifInDiscards ifInErrors ifInUnknownProtos ifOutOctets ifOutUcastPkts if...

Страница 330: ...tcpAttempFails tcpEstabResets tcpCurrEstab tcpInSegs tcpOutSegs tcpRetransSegs tcpConnState tcpConnLocalAddress tcpConnLocalPort tcpConnRemAddress tcpConnRemPort tcpInErrs tcpOutRsts UDP UdpInDatagra...

Страница 331: ...ootprintFactor cellularIP cellularSignal cellularSignalPercent Power Meter1 On Com3 com3pm1Index com3pm1Interface com3pm1ModbusID com3pm1Name com3pm1PTIndex com3pm1PTValue com3pm1PTIndex com3pm1CTValu...

Страница 332: ...ed information above but with prefix com4pm16 instead The SNMP Variables naming rule of the power meters on LAN The Power Meter1 SNMP Variables are similar as listed information above but with prefix...

Страница 333: ...rule of the I O modules on Com3 The I O Module1 SNMP Variables are shown as above with prefix com3io1 the I O Module2 SNMP Variables are similar to listed information above but with prefix com3io2 in...

Страница 334: ...hMaxDemandM com1pm1ChElectricityD com1pm1ChElectricityM com1pm1ChElectricityY com1pm1DOIndex com1pm1DOName com1pm1DOValue com1pm1HarmonicSubmeterIndex com1pm1HarmonicSelector com1pm1HarmonicVTHD com1p...

Страница 335: ...ndex com1io1CoilOutputName com1io1CoilOutputValue com1io1CoilOutputModbusAdd com1io1CoilOutputAdvFunction com1io1InputRegIndex com1io1InputRegName com1io1InputRegValue com1io1InputRegModbusAdd com1io1...

Страница 336: ...isted information above but with prefix com2io16 instead The SNMP Variables naming rule of the I O modules on LAN The I O Module1 SNMP Variables are similar as listed information above but with prefix...

Страница 337: ...eive the specific topics to complete the action Following will list the format of Public topic to the related output channel of module and Internal Register DO channel of ICP DAS XV Board Topic Prefix...

Страница 338: ...e module_no coil_output channel_ address Prefix Please refer to 9 3 MQTT Setting interface com3 com4 or lan module_no 1 16 channel_address 0 99999 Message 0 or 1 The Holding Register channel of others...

Страница 339: ...indicates the message published by PMC PMD to inform IoT Cloud platform the update of the power data or I O channel data CHANNEL_OUTPUT If PMC PMD receives the message in the type of CHANNEL_OUTPUT th...

Страница 340: ...kw kW kvar kvar kva kVA pf PF kwh kWh kvarh kvarh kvah kVAh kw_now Actual Demand kw_predict Forecast Demand maxkw_hour Max Demand Hourly maxkw_day Max Demand Daily maxkw_month Max Demand Monthly mwh_...

Страница 341: ...following is the format to publish a message with the kwh value of Loop 2 which resides at the PM 3114 power meter with module number 5 to IoT Cloud platform The power module is connected to the COM3...

Страница 342: ...a format of the received message from IoT Cloud platform it is used to change the value of AO channel 1 of XV Board of PMC 5231 to 3 6 The following is a format of the received message from IoT Cloud...

Страница 343: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 328 msg_type CHANNEL_OUTPUT if_type 1 com_port 4 module_no 3 ch_type ao ch_addr 2 nickname fan speed value 5 0...

Страница 344: ...MC PMD setting for the Network connection to the IoTstar i Launch a Browser to open PMC PMD Web page Login into the PMC PMD and enter the System Setting Page ii Make sure the firmware version of the P...

Страница 345: ...PMC 523x PMC 224x PMD Series User Manual 330 iii Click the Network Setting button on the Sub function area to enter the Network Setting Page iv Visit Cloud Manager System Setting section and click En...

Страница 346: ...ovided Please Note The ICP DAS IoTstar Create Account is currently disabled and the function is reserved Please do not click on this option vi After all settings are completed click Save button to sav...

Страница 347: ...atus field check Enable to enable the Cloud Upload function and select the Data Log file type you would like to upload After all settings are completed click Save button to save the setting and then c...