“Function Status” to enable the connection to the ICP DAS IoTstar.
v.
Select "User-defined IP address" and in the "Server Address" field, input the IP
address or Domain Name of the PC or Platform (with IoTstar installed). Enter
the login username and password in the “Username” and “Password” fields.
PMC/PMD will login to the IoTstar by the information provided.
Please Note
:
The "ICP DAS IoTstar - Create Account" is currently disabled
and the function is reserved. Please do not click on this option.
vi.
After all settings are completed, click “Save” button to save the changes.
vii.
If the "Connection status" field shows the "Connected" message, it means the
connection between the PMC/PMD controller and IoTstar is in normal status.
The authorized users now can login to the IoTstar (with the username and
password set in “Step V”) to perform remote monitoring and maintenance of
the PMC/PMD.
viii.
To enable the PMC/PMD's Power meter and I/O Module Data logger files