ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
145
xiii.
The value in "Periodical Publish Interval" field defines the time
interval (in second) to send all Publish Topics with the “Periodical
Publish” attribute automatically and periodically. If the value of the
"Periodical Publish Interval" field is 0, it means the “Periodical
Publish” operation is disabled.
xiv.
The “Topic Prefix” field is for setting up a string as Topic Prefix. The
prefix can be used in the Publish Topic or Subscribe Topic to simply
the Topic editing. The default string of the “Topic Prefix” will be the
model name of the PMC/PMD. If there are more than one PMC/PMD
controllers in a system for MQTT connection, please remember to
change the “Topic Prefix” setting to distinguish the Publish
Topic/Subscribe Topic setting of each PMC/PMD controller.
xv.
The lower half area of the MQTT Broker Setting Page is for the
Publish Message and Subscribe Topic setting. User can click the
“Publish” tab or “Subscribe” tab on the right-top corner of “Publish &
Subscribe Setting” to edit the Publish Message and Subscribe Topic.
The Interface will be shown as below:
Figure9-9 :
Publish Message and Subscribe Topic setting page
xvi.
Click the “Publish” tab to edit the Publish Message. Click on “Add
new Publish Message” to add a new Publish Message. The Interface
will be shown as below:
Содержание PMC-523 Series
Страница 1: ...ICP DAS PMC 523x PMC 224x PMD Power Meter Concentrator Series User Manual Version 3 2 4...
Страница 54: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 39 Figure5 32 Energy Usage Breakdown by Circuit Group Chart...
Страница 165: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 150 Figure9 14 The Import of MQTT Topic...
Страница 205: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 190 Figure10 53 PUE Setting Page 2...