ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
129
EventLog \ Event-2013-05-23.log
20130523 indicates that the first event recorded in the Event Log file is
starting from May 23, 2013
8.6
The format of the Power Data Logger file
The power data logger files generated are in CSV format. Each line
represents one record; each field in the line is separated by a comma. The
data sequences from left to right in the line of the power data are as follows:
PM-2133 / PM-3133(-MTCP) / PM-3033(-MTCP) Data Logger Field
Date, Time, Power meter ID,
Phase A [
Voltage, Current, kW, kvar, kVA,
PF, kWh, kvarh, kVAh, Daily tot. Electricity
(kWh)
, Current demand(
15/30/60
mins)
]
,
Phase B [
Voltage, Current, kW, kvar, kVA, PF, kWh, kvarh, kVAh,
Daily tot. Electricity
(kWh)
, Current demand
(15/30/60 mins)
]
,
Phase C
[
Voltage, Current, kW, kvar, kVA, PF, kWh, kvarh, kVAh, Daily tot.
Electricity
(kWh)
, Current demand
(15/30/60 mins)
]
,
Average/Total [
Voltage,
Current, kW, kvar, kVA, PF, kWh, kvarh, kVAh, Daily tot. Electricity
(kWh)
,
Current demand
(15/30/60 mins)
]
,
[Reserved Field].
PM-2134 / PM-3112(-MTCP) / PM-3114(-MTCP) Data Logger Field
Date, Time, Power meter ID,
CT1 [
Voltage, Current, kW, kvar, kVA, PF,
kWh, kvarh, kVAh, Daily tot. Electricity
(kWh)
, Current demand(
15/30/60
mins)
]
,
CT2 [
Voltage, Current, kW, kvar, kVA, PF, kWh, kvarh, kVAh,
Daily tot. Electricity
(kWh)
, Current demand
(15/30/60 mins)
]
,
........
,
CTN
[
Voltage, Current, kW, kvar, kVA, PF, kWh, kvarh, kVAh, Daily tot.
Electricity
(kWh)
, Current demand
(15/30/60 mins)
]
,
[Reserved Field].
PM-4324(-MTCP) / PM-4324A(-MTCP) Data Logger Field
Date, Time, Power meter ID,
Submeter 1
Phase A/CT1 [
Voltage, Current,
kW, kvar, kVA, PF, kWh, kvarh, kVAh, Daily tot. Electricity
(kWh)
, Current
demand(
15/30/60 mins)
]
,
Phase B/CT2 [
Voltage, Current, kW, kvar, kVA,
PF, kWh, kvarh, kVAh, Daily tot. Electricity
(kWh)
, Current demand
(15/30/60
mins)
]
,
Phase C/CT3 [
Voltage, Current, kW, kvar, kVA, PF, kWh, kvarh,
kVAh, Daily tot. Electricity
(kWh)
, Current demand
(15/30/60 mins)
]
,
Average/Total [
Voltage, Current, kW, kvar, kVA, PF, kWh, kvarh, kVAh,
Daily tot. Electricity
(kWh)
, Current demand
(15/30/60 mins)
]
,
Submeter 2
Содержание PMC-523 Series
Страница 1: ...ICP DAS PMC 523x PMC 224x PMD Power Meter Concentrator Series User Manual Version 3 2 4...
Страница 54: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 39 Figure5 32 Energy Usage Breakdown by Circuit Group Chart...
Страница 165: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 150 Figure9 14 The Import of MQTT Topic...
Страница 205: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 190 Figure10 53 PUE Setting Page 2...