![ICP DAS USA I-7021 Скачать руководство пользователя страница 86](http://html1.mh-extra.com/html/icp-das-usa/i-7021/i-7021_user-manual_3685406086.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
86
2.16 $AA6
Description:
Reads the status of the digital input channels..
Syntax:
$AA6[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be read (00 to FF)
6 Command to read the digital input channels
Response:
Valid command:
!(Data)[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command or
invalid type code
AA
Address of the responding module (00 to FF)
(Data)
Status of the digital input channels, a two-digit
hexadecimal value followed by 0000.
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.