I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
166
3.11 M-7024R Address Mappings
Address Description
Attribute
40001 ~
40004
Analog output value
R/W
40065 ~
40068
Analog output read back
R
40097 ~
40100
Safe output value
R/W
40129 ~
40133
Counter value of digital input
R
40193 ~
40196
Power on output value
R/W
40481
Firmware version (low word)
R
40482
Firmware version (high word)
R
40483
Module name (low word)
R
40484
Module name (high word)
R
40485
Module address, valid range: 1 ~ 247 R/W
40486
Bits 5:0
Baud rate, 0x03 ~ 0x0A
Code
0x03
0x04
0x05
0x06
Baud
1200
2400
4800
9600
Code
0x07
0x08
0x09
0x0A
Baud
19200 38400 57600 115200
Bits 7:6
00: no parity, 1 stop bit
01: no parity, 2 stop bits
10: even parity, 1 stop bit
11: odd parity , 1 stop bit
R/W
40487
Type code
R/W
40488
Modbus response delay time in ms,
valid range: 0 ~ 30
R/W
40489
Host watchdog timeout value, 0 ~ 255,
in 0.1s
R/W
40492
Host watchdog timeout count, write 0
to clear
R/W